background image

Internet Version for Reference Only

 

Bradford White

Page 28

Copper Brute II

Page 29

signal to these terminals. The control energizes the 

heater pump (if equipped), energizes the Pmp-Pmp 

terminals, and turns on the heater pump segment in the 

display. The control also turns on stage 1 of the heater. 

Section 5.3 contains important information about 

external staging controls and building automation 

systems. 

Other wiring methods may be unsafe. The 

wiring in Section 5.3 of this manual must be used.

6.3.11 Limit Controls

In addition to the temperature control, Copper 

Brute II appliances are fitted with a manual reset 

high limit and an automatic reset high limit. These 

are located near the rear of the cabinet on the right 

side, behind the slide out drawer (see Figure 17). 

Both controls should be set at least 25°F higher than 

the target temperature to avoid short cycling. To set 

these controls, remove the control panel cover and 

pull the control panel out to gain access. Appliances 

with reversed heat exchangers have the limit controls 

relocated to the left side of the appliance. The left 

access door must be removed to gain access to the 

limit controls on these appliances.

6.3.12 Advanced Programming Mode

Advanced programming mode allows the 

installer to set the temperature control for proportional 

staging. In advanced programming mode, the 

interstage differential, interstage delay, interstage on 

and off delay, and minimum time on and off are all set 

manually.

NOTE:

 Advanced programming mode is rarely 

required. It is intended for advanced installers, 

and only when the application demands such 

programming.

To enter advanced programming mode, remove 

the bezel on the temperature control by pulling out at 

the bottom. Remove the small Phillips head screw to 

access the dip switch. The dip switch is mounted on a 

circuit board. 

Locate the letter “A” 

on the circuit board 

and 

slide the corresponding dip switch toward the letter 

“A”. The default setting of this dip switch is toward 

the “OFF” lettering on the circuit board.

6.4  Operating the Burner and Set Up

6.4.1  Set Up for 0 to 2500 Feet Altitude

The Copper Brute II appliance utilizes a modular 

design to achieve its stage-firing. The setup must be 

checked before the unit is put in operation. Problems 

such as failure to start, rough ignition, strong exhaust 

odors, etc. can be due to improper setup. Damage to 

the Copper Brute II resulting from improper setup is 

not covered by the limited warranty.

1.      Using this manual, make sure the installation 

is complete and fully in compliance with the 

instructions.

2.      Determine that the appliance and system are 

filled with water and all air has been bled from 

both. Open all valves.

3.      Observe all warnings on the Operating 

Instructions label and turn on gas and electrical 

power to appliance.

4.      Switch on the heater power switch located on the 

right side of the unit.

5.      The heater will enter the start sequence, as long 

as the unit is being called for heat. The blower 

and pump come on for pre-purge, then the ignitor 

warm-up sequence starts and after the ignitor 

warm-up is complete and all safety devices are 

verified, the gas valves open. If ignition doesn’t 

occur, check that there is proper gas supply. 

Wait 5 minutes and start the unit again. During 

initial start up, air in the gas line may cause the 

heater to "lock out" during the first few trials 

for ignition. Depending on the ignition modules 

installed, the manual reset button on the ignition 

modules may need to be depressed to restart the 

heater.

6.      When the unit is running, the supply gas pressure 

must be checked. Inlet gas pressure must not 

exceed 13" W.C. (3.2kPa). The minimum inlet 

gas pressure is 5" W.C. (1.2kPa).

7.      Once the inlet gas pressure is verified, the 

outlet gas pressure from each valve (manifold 

gas pressure) must be checked, and adjusted, if 

necessary. The manifold gas pressure must be 

2.5" W.C. (0.62kPa).

8.      Complete the setup by checking the CO

2

 at the 

outlet of the unit. The CO

2

 should be 8% for 

natural gas, or 9.2% for propane.

9.      After placing the heater in operation, the 

Burner Safety Shutoff Device must be tested

To test: 

         (a)    Close gas shutoff valve with burner 

operating.

         (b)    The flame will go out and blower will 

continue to run for the post purge cycle. 

One additional attempt to light will follow. 

Ignition will not occur as the gas is off. The 

ignition control will lockout, and will have 

to be reset before the unit will operate.

         (c)    Open gas shutoff valve. Restart the 

appliance. The ignition sequence will 

start again and the burner will start. The 

appliance will return to its previous mode 

of operation.

NOTE:

 Models 1000 - 2000 have two ignition controls 

and two ignitors, which work independently of one 

another. If the ignition control for stages 1 and 2 fails 

to properly light the main burners for those stages, the 

second ignition control will still be active, and will be 

able to energize stages 3 and 4. This, of course, will 

only occur if all other safety devices confirm that the 

unit will run in a safe condition.

Summary of Contents for BWCV

Page 1: ...ort Ne pas entreposer ni utiliser d essence ni d autres vapeurs ou liquides inflammables dans le voisinage de cet appareil ou de tout autre appareil QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ Ne pas te...

Page 2: ...ting Instructions 6 1 Sequence of Operation 20 6 2 Programming the Temperature Control 20 6 2 1 System Piping 21 6 2 2 Choosing the Mode 21 6 2 3 Programming 21 6 2 4 Choosing the Mode for your Applic...

Page 3: ...actory or local factory representative with any issues or questions regarding this equipment Experience has shown that most operating issues are caused by improper installation The Copper Brute II is...

Page 4: ...Verify receipt of all packages listed on the packing slip Inspect everything for damage immediately upon delivery and advise the carrier of any shortages or damage Any such claims should be filed with...

Page 5: ...199 393 4 101 101 8 26 303 4 78 291 2 75 83 4 22 83 4 22 91 231 8 20 12 30 8 20 1750 89 226 441 2 113 101 8 26 303 4 78 291 2 75 83 4 22 83 4 22 101 256 8 20 14 36 8 20 2000 991 2 253 493 4 126 101 8...

Page 6: ...opper Brute II water heaters must have provisions for combustion and ventilation air in accordance with section 5 3 Air for Combustion and Ventilation of the National Fuel Gas Code ANSI Z223 1 or Sect...

Page 7: ...able 3 Combustion Air Openings 2 1 2 Intake Combustion Air The combustion air can be taken through the wall or through the roof When taken from the wall it must be taken from out of doors by means of...

Page 8: ...blocked common vent may lead to serious injury or death Safety devices must be implemented to prevent blocked common vent operation If safe operation of all appliances connected to a common vent canno...

Page 9: ...air supply inlet 3 feet 91 cm above if within 10 feet 3 m 6 feet 1 83 m horizontally Vent termination not allowed in this location Vent termination not allowed in this location for category IV applia...

Page 10: ...ther nearby objects Vent products may damage such surfaces or objects 7 If the water heater uses ducted combustion air from an intake terminal located on the same wall locate the vent terminal at leas...

Page 11: ...iciencies which could cause an unsafe condition 3 Insofar as it is practical close all building doors and windows and all doors between the space in which the appliances remaining connected to the com...

Page 12: ...ual shutoff valves in accordance with state and local requirements 6 A sediment trap must be provided upstream of the gas controls 7 All threaded joints should be coated with piping compound resistant...

Page 13: ...t can be used for more full featured domestic water heating control To get these features you must provide a location for the additional sensor It can be strapped to a pipe from 1 to 4 diameter or ins...

Page 14: ...M 17 1 Grains Per Gallon KEY S SOFT N NORMAL H HARD 1 THROUGH 7 5 7 6 THROUGH 17 OVER 17 LOCATION OF FACTORY MOUNTED PUMP 2 5 3 4 7 MINIMUM INLET WATER TEMPERATURE IS 120 F Table 8 Water Flow Requirem...

Page 15: ...BACK FLOW PREVENTER MAY BE REQUIRED CHECK LOCAL CODES 4 THERMAL EXPANSION TANK MAY BE REQUIRED CHECK LOCAL CODES 5 WHEN USING FACTORY MOUNTED PUMP MAX PIPE LENGTH IS 30 FEET TOTAL SIX 90 ELBOWS FULL...

Page 16: ...NG MUST BE BASED UPON WATER HARDNESS AT JOB SITE 1 OPTIONAL CWMU RECIRC LINE LOCATION 2 LOCATE PENNANT DHW SENSOR OR REMOTE AQUASTAT WELL IN LOWER 1 3 OF TANK 3 BACK FLOW PREVENTER MAY BE REQUIRED CHE...

Page 17: ...SITE 1 OPTIONAL CWMU RECIRC LINE LOCATION 2 LOCATE PENNANT DHW SENSOR OR REMOTE AQUASTAT WELL IN LOWER 1 3 OF TANK 3 BACK FLOW PREVENTER MAY BE REQUIRED CHECK LOCAL CODES 4 THERMAL EXPANSION TANK MAY...

Page 18: ...pipe or dielectric unions may isolate the heater electrically Service and maintenance personnel who work on or around the heater may be standing on wet floors and could be electrocuted by an ungrounde...

Page 19: ...n 5 3 for important information about external staging controls and building automation systems System Heat Demand Remove the jumper across the COM D and Ht D terminals and connect the zone pump or va...

Page 20: ...flow sensing circuit if this pressure exceeds a maximum value If airflow is not proven the ignition module will lockout The ignition module checks that the ignitor current has reached a minimum value...

Page 21: ...eater s temperature control continuously samples the inlet outlet and target temperatures Mode 6 is the Manual mode and the AUTO MAN switch must be moved to the MAN position An external control such a...

Page 22: ...GET temperature See section 6 3 3 for more information BOIL MAX Boiler Maximum Temperature This setting tells the Temperature Control to limit the maximum outlet temperature to this setting or below a...

Page 23: ...r ADJUST mode Figure 10 Press Item to select the programming item and the arrow keys to adjust the setting TARGET TANK is desired tank temperature Recommended settings with a desired tank temperature...

Page 24: ...if the pump does not run continuously Mechanical aquastat in a domestic hot water storage tank Remove the jumper from the Com D and HtD terminals and connect the aquastat s leads to these terminals T...

Page 25: ...ls If the ComD and HtD terminals are left jumpered the control will always see a heat demand and remain in Dem mode with the heater pump running continuously See Section 5 2 for more information A sec...

Page 26: ...9 C to protect the unit from condensing on the heat exchanger see Figure 14 6 3 1 Differential Differential has an abbreviated name of DIFF An on off heat source must be operated with a differential i...

Page 27: ...the control will activate the Dem segment in the display The control energizes the pump on pump mounted heater and energizes the Pmp Pmp terminals The heater pump segment is turned on in the display...

Page 28: ...he typical coldest temperature of the year where the building is located This temperature is used when doing heat loss calculations for the building Boiler Design BOIL DSGN The BOIL DSGN temperature i...

Page 29: ...oper setup is not covered by the limited warranty 1 Using this manual make sure the installation is complete and fully in compliance with the instructions 2 Determine that the appliance and system are...

Page 30: ...being adjusted is energized by a call for heat from the staging control After all of the gas valve manifold pressures have been set the CO2 or O2 must be reset CO2 or O2 will have changed when the man...

Page 31: ...gory III ensure that all joints are sealed properly If joints need to be resealed completely remove existing sealing material and clean with alcohol Apply new sealing material and re assemble 7 2 Appl...

Page 32: ...of gas valve connections 7 2 4 Manual Reset High Limit Control The high limit switch is manual reset switch with an adjustable set point up to 200 F 93 C To replace the switch shut off the 120 volt p...

Page 33: ...t air for complete combustion and black carbon sooting is seldom experienced If sooting is suspected view ports for inspection of the heat exchanger are provided on both sides of the heater They are l...

Page 34: ...unctioning properly then burners should be inspected There should be no distortion or perforations in the burners outside of the active burner port area Replace if indicated 8 3 Short Cycling Short cy...

Page 35: ...able to read the heater outlet sensor due to an open circuit In this case if the heater inlet sensor is present and operational the control will operate using the heater inlet sensor Otherwise the co...

Page 36: ...in Figure 19 Ignition module 1 handles stages 1 and 2 and ignition module 2 handles stage 3 The single blower is energized directly through the inducer terminals of either ignition module The 24V pow...

Page 37: ...Internet Version for Reference Only Copper Brute II Page 37 Figure 18 Copper Brute II 500 750 Ladder Diagram SECTION 9 Wiring Diagrams...

Page 38: ...Internet Version for Reference Only Bradford White Page 38 Figure 19 Copper Brute II 1000 Ladder Diagram...

Page 39: ...Internet Version for Reference Only Copper Brute II Page 39 Figure 20 Copper Brute II 1250 2000 Ladder Diagram...

Page 40: ...ternet Version for Reference Only Bradford White Page 40 Figure 21 Copper Brute II 500 1000 Wiring Schematic Note Positions of field wiring terminals may vary but terminal designations are as indicate...

Page 41: ...ernet Version for Reference Only Copper Brute II Page 41 Figure 22 Copper Brute II 1250 2000 Wiring Schematic Note Positions of field wiring terminals may vary but terminal designations are as indicat...

Page 42: ...Internet Version for Reference Only Bradford White Page 42 Figure 23 Field Wiring HEATER HEATER Note Positions of field wiring terminals may vary but terminal designations are as indicated...

Page 43: ...MODE 5 COM D HT D COM D HT D COM D HT D SET D COM D HT D SET D S C2 SUP S HEATER IN HEATER OUT LWCO FLOW SWITCH ABOVE DIAGRAM SHOWS WIRING COMMON TO ALL CONTROL MODES S C2 SUP S OD S S C2 DHW TSTAT H...

Page 44: ...O 2C 1C 2NO 1NO Jumper 2C 1C Copper Brute II 1250 1500 1750 2000 4 Stage Heater 2C 1C 1 stage Jumper 2C 2NO 2 stage 1NO 1C 2NO 1NO 2 stage using 1 control output h eater 2 stage using 2 control output...

Reviews: