Communication
KNX Bus
Power supply
via the KNX bus, 29 V dc SELV
Auxiliary power supply
230Vac
Bus cable
KNX TP1
Bus current consumption
10 mA max
Command elements
1 miniature programming key
4 push-buttons for local relay command
Display elements
1 red programming LED
4 green LEDs for signalling output status
Actuation elements
4 16AX relays with NO potential free contact
Maximum switchover current
16 A (AC1)
16AX (140 µF ref. EN 60669-1) fluorescent loads
with maximum surge current 400A (200 µs)
Maximum power for load type
Incandescent lamps (230 Vac): 3000W
Halogen lamps (230Vac): 3000W
Loads controlled by toroidal transformers: 3000W
Loads controlled by electronic transformers: 2000W
Low consumption lamps
(compact fluorescent lamps): 80x23W
Maximum dissipated power
5W
Ambit of use
Indoors, dry places
Operating temperature
-5 to +45 °C
Storage temperature
-25 to +70 °C
Relative humidity
Max 93% (non condensative)
Bus connection
Coupling terminal, 2 pins Ø 1 mm
Electrical connections
Extractable screw terminals, maximum cable
section: 4mm
2
Protection ratings
IP20
Dimension
4 DIN modules
Reference standard
Low voltage directive 2006/95/EC
Electromagnetic Compatibility Directive
2004/108/EC, EN50428, EN50090-2-2
Certifications
KNX
19
E
N
G
L
I
S
H
TECHNICAL DATA