6
Flash for ON
Status response
Each channel can deliver a status response, depending on
the parameter settings. This always conveys the actual state
of the output (1= relay closed; 0= relay opened).
Parameters
Per channel: Select the relay mode “flash for ON” or
“flash for OFF”
Channel X: General
Parameter
Setting
Relay operation
make contact
break contact
changeover contact (channel 1:
make contact / channel 2: break
contact)
flash for ON
flash for OFF
Set the flashing interval for the device.
Flashing interval
Parameter
Setting
Flashing interval base
100 ms
1 s
1 min
1 hr
Flashing interval factor [5-255]
10
adjustable in single steps
open
1
0
closed
Relay
Status
actuated
not actuated
Switch (changeover contact for channel 1/2)
Status response
If two channels are combined into a changeover contact,
there is only one status feedback object when the status
response function is active.
This object always conveys the switching state of the
odd-numbered channel e.g. “1” (1= relay closed; 0= relay
opened).
Parameters
Per pair of channels: Select the relay mode “changeover
contact (channel 1: make contact / channel 2: break
contact)”
Channel X: General
Parameter
Setting
Relay operation
make contact
break contact
changeover contact (channel 1:
make contact / channel 2: break
contact)
flash for ON
flash for OFF
- Relay operation: flashing indicator
In the flashing indicator function, the relay opens and
closes automatically. A common flashing rate can be set for
all the channels via the “Flashing interval” parameter. The
frequency is calculated by multiplying a base value with a
factor.
L
L
Important
No short switching times may be parameterised
under load (see the technical data for the switch
output)
It can be selected whether the channel flashes for the value
“ON” (actuated) or “OFF” (not actuated). The value is the
product of combining the disable/higher priority function
with the switch object.
open
t
t
1
0
remains
open
is
closed
KNX
telegram
Relay status of
channel A
closed
t
remains
closed
is
opened
open
t
1
0
KNX
telegram
Relay status of
channel A
closed
open
t
remains
open
is
closed
Relay status of
channel B
closed
t
remains
closed
is
opened
open
Relay status of
channel B
closed
Switching on