14
Parameters
Per channel: Switch on the ON/OFF delay, staircase
lighting function and disable function.
Channel X: General
Parameter
Setting
Disable function
switched off
switched on
ON delay
switched on
switched off
OFF delay
switched on
switched off
Staircase lighting function
switched off
switched on
Per channel: Set the disable function.
Channel X: Disable
Parameter
Setting
Disable function for
Disable object = 0
Disable object = 1
Value of disable object after bus
voltage recovery
1
0
Reaction at blocking
no change
changes state
actuated
not actuated
flashes
Reaction at activation
no change
follows switch object
actuated
not actuated
Reaction at activation (with active
staircase lighting function)
follows switch object
not actuated
Per channel: Set the ON and OFF delay.
Channel X: Times
Parameter
Setting
Time base for ON delay -
100 ms
1 s
1 min
1 hr
Factor for ON delay
(1-255)
3
adjustable in single steps
ON delay is
not retriggerable
retriggerable
Time base for OFF delay -
100 ms
1 s
1 min
1 hr
Factor for OFF delay
(1-255)
120
adjustable in single steps
OFF delay is
not retriggerable
retriggerable
Set the flashing interval for the device if required.
Flashing interval
Parameter
Setting
Flashing interval base
100 ms
1 s
1 min
1 hr
Flashing interval factor [5-255]
10
adjustable in single steps
L
L
Important
No short switching times may be parameterised
under load (see the technical data for the switch
output)
- Disable function with switching delay/staircase light-
ing function
When the disable function is activated, it always switches
in the required direction without a delay. When it is deacti-
vated, the actuator likewise switches to the required state
without a delay. The last switching telegram is saved during
a disable function and any delay periods or staircase timers
continue to run.
Disable function for: Disable object = 1; Value of disable object after bus
voltage recovery: 0; Reaction at blocking: no change; Reaction at activa-
tion: follows switch object: Relay: make contact
Communication objects
The following communication objects can be selected:
Per channel:
Function
Object name
Type
Prio
Flags
Behaviour
Channel X
Switch object
1 bit
Low
CW
Receive
Channel 1,
2,...
Disable object
1 bit
Low
CW
Receive
KNX
telegram,
switch object
t
t
Relay status
closed
1
open
1
t staircase
t staircase
1
t staircase
KNX
telegram,
disable object
t
1
0
1
0
1
0
disabled
disabled
disabled