3.2 Installation Specification 

 

No. 

Description 

Valve Inlet 

Strainer 

Water Meter 

Valve Outlet 

3.3 Before Installation   

The pipe must be completely cleaned before installing the ultrasonic water meter to prevent 
the debris from damaging the water meter; 

Ultrasonic  water  meter  is  an  expensive  precision  instrument.  Care  must  be  taken  when 
transporting.  It  is  forbidden  to  directly  lift  the  meter  head  or  sensor  line;  it  is  strictly 
prohibited  to  approach  a  higher  temperature  heat  source  (such  as  electric  welding  to 
prevent battery explosion and injury and damage to the instrument); 

The  installation  position  of  the  ultrasonic  water  meter  should  pay  special  attention.  The 
water meter should be avoided to be installed at the upper end of the pipeline (there will be 
bubbles in the pipe), avoiding installation near the elbow (which will generate vortex flow), 
and  should  be  kept  away  from  pumps  and  other  equipment  (which  will  cause  pulsating 
flow); 

The connecting pipe at the upstream and downstream of the ultrasonic water meter shall be 
the same as the diameter of the water meter and shall not be reduced in diameter; 

The  direction  indicated  by  the  arrow  on  the  surface  of  the  ultrasonic  water  meter  is  the 
direction of water flow, and shall not be reversed; 

It  is  recommended  that  the  front  end  of  the  ultrasonic  water  meter  be  equipped  with  a 
strainer of the corresponding diameter; the valve is installed in front of the meter and it can 
be separated from the meter body for future maintenance and repair. 

 

Summary of Contents for B39 VW Bulk

Page 1: ...www bovetech com Installation User Guide B39 VW Bulk Ultrasonic Water Meter Read this Guide before installing the meter...

Page 2: ...f this manual to ensure the accuracy of its contents However should you have any questions or find any errors please contact BOVE TECHNOLOGY Copying or reproducing all or any part of the contents of t...

Page 3: ...EQUIREMENTS FOR INSTALLATION ENVIRONMENT 5 3 2 INSTALLATION SPECIFICATION 6 3 3 BEFORE INSTALLATION 6 3 4 COMMON ERROR INSTALLATION EXAMPLES 7 3 5 INSTALLATION OF NON RETURN VALVE 9 3 6 AFTER THE INST...

Page 4: ...asure the average velocity along the path of an emitted beam of ultrasound by averaging the difference in measured transit time between the pulses of ultrasound propagating into and against the direct...

Page 5: ...wer supply requirements See part 4 Power supply Pulse input device class N A Max permissible flow sensor signal Pulse rate N A Output signal for normal operation M Bus Infrared RS485 LoRa Pulse output...

Page 6: ...rror in upper flow rates range Q2 Q Q4 2 at 30 C 3 at 30 C Maximum permissible error in lower flow rates range Q1 Q Q2 5 Scale interval m3 0 01 Capacity of calculator 99999 99 999 Type of liquid Water...

Page 7: ...ply Battery One 3 6V Lithium Battery Battery Life 6 Years 24V DC External supply for special version Optional Mechanical Specification Meter body Cast steel 2 4 Data Storage 1 Accumulated flow for the...

Page 8: ...ng term submergence provided that all cable unions have been correctly mounted and that the plastic cover has been properly fastened Make sure the meter is installed sufficiently far away from possibl...

Page 9: ...onic water meter should pay special attention The water meter should be avoided to be installed at the upper end of the pipeline there will be bubbles in the pipe avoiding installation near the elbow...

Page 10: ...ontally the direction of the calculator should be upwards If the direction of the calculator is facing to the side the two transducers will not be on one level and the transducer at the high point may...

Page 11: ...meter is installed at the elbow it must be ensured that the distance between the front straight pipe is 5 pipe diameter and the rear straight pipe is 3 pipe diameter Otherwise the meter may not be mea...

Page 12: ...splay information When the response thresholds are exceeded and the flow rate is positive the volume is summated Make the segment test in order to displays all display segments for test purposes The o...

Page 13: ...rity in case of the pulse output If the meter is read out via M bus the allowed mean frequency of reading must not be exceeded Any more reading is not allowed and may result in a damage to meter The M...

Page 14: ...may press the button to read the meter information such as Accumulated volume current flow rate etc The following information is displayed in order by short pressing the button accumulated flow insta...

Page 15: ...Copyright 2018 Bove Intelligent Technology Co Ltd 12 17 6 1 2 Main Menu Shortly pressing the button to display items under the Main Menu one by one in the following order to check the measurement data...

Page 16: ...Copyright 2018 Bove Intelligent Technology Co Ltd 13 17 6 1 3 Menu E Shortly pressing the button to display items under Menu E one by one in the following order to check the meter information...

Page 17: ...8 Bove Intelligent Technology Co Ltd 14 17 6 1 4 Menu I This Menu shows history date records of last 24 months Click the button to select the month then the month monthly flow consumption will be disp...

Page 18: ...cally when flow is zero and starts to exceed the preset value then the current accumulated value is clear to zero Also the value can be reset by long pressing the button over 2 seconds The meter exit...

Page 19: ...elf diagnosis and can display various faults Visual indication on the LCD display in the event of an warning Permanent visual indication on the LCD Fault Meaning How to handle the error 1 Low battery...

Page 20: ...rompt services and reliable products to our global customers Bove is committed to address the unique challenges that the residential and industry are facing including increasing customer demand water...

Reviews: