background image

4

CS 2500

-  Connecter la RJ45 " Control Out " sur la RJ45 " Control In "  corres-

pondante du CS2003

-  Connecter la RJ45 " Audio Out " sur la RJ45 " Audio In "  corres-

pondante du CS2003

-  Configurer les CS2003
-  Poser les pupitres GX2500 sur leur plan d’utilisation
-  Connecter l’alimentation des GX2500 issue bornier " OUT " de la

CS 2500

-  Configurer les pupitres
-  Connecter la RJ45 " Control / Audio " sur la RJ45 " Control / Audio

" correspondante de la GX2500

-  Relier le bornier "ALARM UNIT" à la CMSI
- Raccorder les borniers " ALARM MODE OUTPUTS D " et " ALARM

MODE OUTPUTS I "

-  Raccorder la RJ45 " Aux Remote Control " 
-  Relier la prise XLR " AUX " à une source de modulation (tuner, CD,

etc…)

-  Relier la prise RS232 à un ordinateur ou un organe de supervision
-  Configurer la 

CS 2500

.

VI - PRINCIPE DE FONCTIONNEMENT

VI - OPERATING PRINCIPLE

6.1. INTERFACE HOMME-MACHINE

L’interface homme-machine est facilitée par l’utilisation de menus
déroulants à choix multiple. L’accès aux menus de configuration
de la

CS 2500 

est protégé par un mot de passe à 4 digits pouvant

être modifié par l’utilisateur.
L’appareil est équipé de touches de navigation, de touches de
fonctions et d’un afficheur 4 lignes de 20 caractères.
Les touches de navigation sont : 
- "  " pour remonter
- " †" pour descendre.
- " C " pour annuler le choix en cours
- " OK " pour valider le choix pointé par le curseur "  "
Les touches de fonction sont : 
- touche " LAMP TEST "
- touche " RESET "
- touche " ACCEPT "
Après la modification d’un paramètre, il faut reinitialiser le

CS 2500

.

6.2. ARCHITECTURE GENERALE DES MENUS

A la mise sous tension, la page " MENU " s’affiche. La figure suivan-

te donne l’architecture des menus.

1. Mode manuel

1-1 Msg évacuation

1-2 Msg alerte

1-3 Msg information

1-4 Msg de test

2. Config CS 2500

(Mot de passe)

2-1 Mise à l’heure

2-2 Entrées sélect.

2-3 Paramétrage AMI

2-4 Paramétrage AMD

2-5 Mot de passe

3. Config système

(Mot de passe)

3-1 Nombre de GX 2500

3-2 Nombre de CS 2003

3-3 Niveau priorités

3-4 Batterie

3-5 Chargeur batterie

4. Prog groupes

(Mot de passe)

4-1 Créer

4-2 Editer

4-3 Supprimer

5. Routage matrice

6. Journal défauts

-  Connect the RJ 45 “Control Out” to the corresponding RJ45

“Control In” of the CS 2003

-  Connect the RJ 45 “Audio Out” to the corresponding RJ45

“Audio In” of the CS 2003

-  Configure the CS 2003 units
-  Place the GX 2500 consoles on their working surface
-  Connect the power supply of the GX 2500 units to the “Out”

terminal of the

CS 2500

-  Configure the consoles
-  Connect the RJ 45 “Control / Audio” to the corresponding

RJ45 “Control / Audio” of the GX 2500

-  Link the “ALARM UNIT” terminal to the FDS
- Plug in the “Alarm Mode Outputs D” and  “Alarm Mode Outputs

I” terminals

-  Plug in the RJ 45  “Aux Remote Control” 
-  Link the XLR “Aux” socket to a signal source (tuner, CD, etc.)
-  Plug RS232 link to a computer or a supervising device.
-  Configure the 

CS 2500

.

1. Manual mode

1-1 Evacuation msg

1-2 Alerte msg

1-3 Information  msg

1-4 Test msg

2. Config CS 2500

(Password)

2-1 Time setting

2-2 Input selection

2-3 Setting AMI parameters

2-4 Setting AMD parameters

2-5 Password

3. Config system

(Password)

3-1 Number of GX 2500s

3-2  Number of CS 2003s

3-3 Level of priority

3-4 Battery

3-5 Battery charger

4. Prog groups

(Password)

4-1 Create

4-2 Edit

4-3 Delete

5. Matrix routing

6. Fault log

6.1. MAN-MACHINE INTERFACE

The man-machine interface is provided by the use of multiple-
choice, pull-down menus. Access to the 

CS 2500

configura-

tion menus is protected by a 4-digit password, which can be
changed by the user.
The unit is equipped with navigation keys, function keys and a
display with 4 lines of 20 characters.
The navigation keys are: 
- "π" to go up
- "†" to go down
- "C " to cancel the present choice
- "OK" to accept the choice indicated by the cursor " "
The function keys are:
-  "LAMP TEST" key
- "RESET"key
- "ACCEPT" key

Reinitialise the 

CS 2500

, after a modification of parameter. 

6.2. GENERAL MENU ARCHITECTURE

When power is switched on the “MENU” page is displayed. 

The following diagram shows the menu architecture.

Summary of Contents for CS 2500

Page 1: ...85 est mat rialis par deux voyants de tra fic en face arri re La centrale CS 2500 est compatible BeeVox_ Ce document n est pas contractuel toute modification pouvant intervenir sans pr avis This docum...

Page 2: ...0 Sortie 24 V 10 A Consommation max 300 mA Temp rature de fonctionnement 0 45 C Dimensions 2U Fig I 425 x 345 x 92 mm Poids 3 4 Kg Option Un jeu de poign es AZ 7 pour le montage en baie 19 Fig II III...

Page 3: ...e 24V alimentation secondaire 24 Connecteur 2 points alimentation 24V alimentation primaire IV BRANCHEMENT DE LA CONNECTIQUE IV WIRING CONFIGURATION V INSTALLATION V INSTALLATION WARNING The unit is n...

Page 4: ...2 Nombre de CS 2003 3 3 Niveau priorit s 3 4 Batterie 3 5 Chargeur batterie 4 Prog groupes Mot de passe 4 1 Cr er 4 2 Editer 4 3 Supprimer 5 Routage matrice 6 Journal d fauts Connect the RJ 45 Contro...

Page 5: ...n de s curit et connect s la CS 2500 6 5 2 Nombre de CS 2003 Ce menu permet de param trer le nombre de modules de sur veillance CS 2003 pr sent dans le syst me de sonorisation de s curit et connect s...

Page 6: ...GX 2500 console number 2 1 Auxiliary input 5 The source with the highest priority is that which has the lowest level In the case of equal priority levels the first to appear has priority The maximum v...

Page 7: ...for auxiliary broadcast selection N broche PinN Type 1 Entr e de s lection 1 Choice 1 input 2 Entr e de s lection 2 Choice 2 input 3 Entr e de s lection 3 Choice 3 input 4 Entr e de s lection 4 Choic...

Page 8: ...in Fault Amplifiers 100V Ligne 100V 24V MONTAUBAN FRANCE RS485 EOL Off On Control In Audio In Control Out Audio Out Stby chain In 1 In 2 In 3 Audio matrix 0 dB Amplifier 0dB Out 1 Out 2 Out 3 Out Stby...

Reviews: