Manual Current relay print JGA2011 

 

Boutronic B.V. 

Boutronic B.V. 

Page - 4 - 

 

s-Gravenzande The Netherlands 

Connection example 

A connection example is given in the image below. 
 

+24 VDC

GND

GND

Power in

Currentrelay

7

8

9

10

11

12

1

2

3

4

5

6

R

o

H

S

 c

o

m

p

lia

nt

T

yp

e

 J

G

A

2

0

11

GN D

4-20m A I N2

R

e

la

y 2

GN D

4-20m A I N1

R

e

la

y 1

+24VD C  IN

+ 24VD C  OU T

w

w

w

.b

o

u

tr

o

n

ic.

n

l

M
ad

e

 in

 th

e

 N

et

h

e

rla

n

d

s

Li

ft

 f

ro

n

h

er

e

 f

o

ac

ce

s

s c

o

n

tr

ol

 

Sensor or signal 1

Sensor or signal 2

 

 

Operation 

The image below simply shows how the JGA2011 works. 
 

Relais 1

4...20 mA

Current in 1

4...20mA

GND

Level

0...100%

4mA = 0%
20mA = 100%

DIP 3 = OFF

DIP 3 = ON

Software level

0...100%

Delay on = 1 sec
Delay off = 1 sec
Hystereis = 1%

Delay on = 1...600 sec
Delay off = 1...600 sec
Hystersis = 1...10%

Relais 2

4...20 mA

Current in 2

4...20mA

GND

Level

0...100%

4mA = 0%
20mA = 100%

DIP 3 = OFF

DIP 3 = ON

Software level

0...100%

Delay on = 1 sec
Delay off = 1 sec
Hystereis = 1%

Delay on = 1...600 sec
Delay off = 1...600 sec
Hystersis = 1...10%

GND

R = 500E

R = 500E

 

 

Current inputs 

A signal of 4… 20 mA is applied to the current inputs. This signal is read in and converted to a 0%  to 
… 100% value.

 

If the current input is lower or equal than 4 mA, the JGA2011 will convert the value to 0%, if the 
current input is higher or equal than 20 mA, the JGA2011 will convert the value to 100%. 
 
Note: The maximum current that may be offered is: 30 mA. 

 

Summary of Contents for JGA2011

Page 1: ...y JGA2011 is checked before sending for correct operation Therefore Boutronic has a warranty period of 1 year The warranty expires if The defect is caused by gross negligence or by improper installati...

Page 2: ...ns 3 Connection example 4 Operation 4 Current inputs 4 Potentiometer 5 Relay 5 Switching delay Relay 5 Change settings 6 Potentiometer 6 DIP switches 6 Setting with the serial menu 6 Relay 1 7 Relay 2...

Page 3: ...Relay1 24VD C IN 24VD C OU T www boutronic nl Made in the Netherlands Li ft front here for ac ces s control P2 Nr Unit Description 1 Connection 7 12 Connection 7 12 see front for type of connections 3...

Page 4: ...GND Level 0 100 4mA 0 20mA 100 DIP 3 OFF DIP 3 ON Software level 0 100 Delay on 1 sec Delay off 1 sec Hystereis 1 Delay on 1 600 sec Delay off 1 600 sec Hystersis 1 10 Relais 2 4 20 mA Current in 2 4...

Page 5: ...d is maximum Relay The relay switches when the corresponding input exceeds the switching threshold Input 1 switches relay 1 and input 2 switches relay 2 Switching delay Relay The switching delay with...

Page 6: ...Use software settings for threshold level Delay and hysteresis 4 Reserved Reserved Setting with the serial menu You can change the settings with the USB port and the Boutronic Studio The Boutronic St...

Page 7: ...1 sec Relay 2 Menu for changing setting relay 2 Value Description range Factory settings Level x Switching level when the relay is switching 0 100 50 Hysteresis x Hysteresis in 1 10 1 Delay on x sec...

Page 8: ...otecting range IP20 Power Description Min Typ Max Unit Remarks Power in 20 24 30 VDC 20 24 24 VAC 1 35 mA Power out 20 30 VDC 2 150 mA 3 1 Note one of the phases is directly connected to the GND 2 Thi...

Page 9: ...1 12 1 2 3 4 5 6 CONTROL Powersupply www boutronic nl GND 24VDC IN Type nummer JGA2011 24VDC OUT 4 20mA in 2 GND Inputs 4 20mA RoHS compliant TA 0 70 C Relay 1 Relay 2 4 20mA in 1 Relay contacts 24VAC...

Reviews: