A flue system must be provided in accordance with BS5410 and
the current Building Regulations. (See Section 1.4).

7.1 CONVENTIONAL FLUE (CF).

See Fig. 4.
Conventional Flue Diameters: 12/14 – 100 mm (4 in.)

15/19 – 100 mm (4 in.)
20/25 – 100 mm (4 in.)
26/32 – 125 mm (5 in.)
32/50 – 125 mm (5 in.)
50/70 – 150 mm (6 in.)

NOTE:

On 50/70 models with flue lengths longer than 12

meters it is recommended that 175mm (7in.) flue pipe is used
from the boiler.

NOTE:

External flues systems must be of the insulated flue type.

The boiler is fitted with a conventional flue locating spigot. The
flue pipe fits into the spigot and should be correctly sealed with
fire cement.

NOTE: 

The size of the flue must never be reduced from the take-

off diameter. An increase in flue size is permissible provided that
the joint is sealed correctly.
When installed the flue should be vertical and contain as few
bends as possible. Where bends are necessary, a maximum of
two are permitted and 135 degree bends should be used.
All brick and masonry chimneys should be lined with a suitable
non-combustible material, properly jointed and able to with-
stand the effects of the working temperature of the appliance
and any condensate which may form.

Down-draught conditions will adversely affect the operation of the boil-
er and must be avoided. Where possible the flue should be extended
beyond the apex of the roof and should always be taken beyond the
eaves of the building. Where down-draught is experienced a suitable
anti down-draught terminal should be fitted to the flue termination.
The natural flue draught must be checked in the flue pipe imme-
diately above the appliance or in the hole provided in the flue
outlet plate. The flue draught should be no less than 0.75 mm
W.g. and no greater than 5.1 mm W.g. If a flue draught greater
than 5.1 mm W.g. is experienced a draught stabiliser should be
introduced into the flue and adjusted to achieve a flue draught
within the specified range.

7.2 Low Level Discharge (LLD)

(See Fig. 5).
The low level flue kit is not designed for use with this appliance
as there is no provision for installation of the flue gas purge
timer. However, where fume odour will not present a problem
(eg boilerhouse/outhouse) the flue kit may be used without the
purge unit. Alternatively, a standard Danesmoor kitchen
appliance or room-sealed utility model should be used.
The LLD kit converts the 12/14, 15/19, 20/25 and 26/32
conventional flue appliances to discharge the combustion
products from the rear of the appliance at low level.
The flue spigot should be removed from the flue outlet plate by

undoing the three retaining screws and the hole blanked off with
the plate provided in the kit.
Detailed instructions for converting the appliance to low level
discharge are supplied with the conversion kit.

NOTE: Under no circumstances may 35 Second Gas Oil be
burned with this type of flue terminal arrangement.

7.3 ROOM SEALED BALANCED FLUE MODEL (RS).

The appliance is supplied ready for installation as a low level
discharge balanced flue system by the simple addition of one of
the flue terminal kit options  shown in Fig. 6.

Details of the installation procedure are included in the Flue
Terminal Installation instructions supplied with the terminal kit.

Alternatively, a range of room-sealed balanced flue kits are available
to convert the appliance to discharge the flue products to the left,
right, at a higher level, or vertically up to a roof height of 4.5 metres.

7.4 Siting the flue terminal

1. 

The flue terminal must be located in a suitable position, as

shown in Fig. 7, such that the products of combustion can be
freely dispersed without  the possibility of the gases entering the
dwelling or that of a neighbouring dwelling. 

2. 

Discharge of flue gases into car ports or narrow passageways

is not recommended.

7. Flue System

9

Fig. 5. Flue Installation (Rear Discharge).

See Fig. 7 for
flue terminating
positions.

80

min.

FLUE GUARD

766

Fig. 4. Flue Installation.

Summary of Contents for WORCESTER DANESMOOR UTILITY 12/14

Page 1: ...D ROOM SEALED BF FLOOR STANDING OIL FIRED PRESSURE JET APPLIANCES INSTALLATION AND SERVICING INSTRUCTIONS THESE INSTRUCTIONS ARE TO BE LEFT WITH THE APPLIANCE This appliance must be installed and serviced by a competent person Worcester supports the Benchmark code of practice ...

Page 2: ...ccording to the manufacturers instructions Without the completion of the Log book manufacturers may refuse to respond to a call out from a householder who will be advised that he or she must call back the installer who has not fulfilled his obligations to record the information required by the initiative It is important that The services and the system are properly flushed as specified The User is...

Page 3: ... mbar 66mbar 195mbar 3 mbar 6 mbar 12 mbar 19 mbar 7mbar 10mbar 24 g hr 35 kg hr 43 kg hr 57 kg hr 85 kg hr 115 kg hr 55 C minimum cut in o 82 C maximum cut out 5 C 100 0 6 C 110 0 6 C CF RS Model POWER SUPPLY HEATING FLOW HEATING RETURN MINIMUM FLUE REQUIREMENT Balanced Flue Kit Balanced Flue Kit Balanced Flue Kit Balanced Flue Kit Section 7 3 Section 7 3 Section 7 3 Section 7 3 N A N A 12 14 15 ...

Page 4: ...0 25 85 000 NOMINAL BOILER RATING AT NORMAL OPERATING TEMPERATURE 20 25 Table 4 Electro Oil Inter B11C Burner See Fig 20 Fuel Nozzle Pump Pressure p s i Fuel Flow Rate Flue Gas Temp C CO2 Approx Air Setting Appliance Input kW Btu hr kW Btu hr Output Kg h l h 28 Sec Kerosene 0 85 80 EH 110 2 36 2 99 225 11 0 11 5 11 28 5 97 000 26 89 000 28 Sec Kerosene 0 85 80 EH 130 2 66 3 37 240 11 0 11 5 12 32 ...

Page 5: ...2 0 12 5 2 75 45 3 154 500 41 140 000 28 Sec Kerosene 1 35 60 S 150 4 6 5 81 220 12 0 12 5 4 75 55 25 188 500 50 171 000 35 Sec Gas Oil 0 85 60 S 210 3 82 4 6 190 12 0 12 5 2 75 45 3 154 500 41 140 000 35 Sec Gas Oil 1 0 60 S 260 4 66 5 61 210 12 5 13 0 6 5 55 25 188 500 50 171 000 NOMINAL BOILER RATING AT NORMAL OPERATING TEMPERATURE 32 50 Table 7 Electro Oil Inter B20C Burner See Fig 22 Conventi...

Page 6: ...e combustion chamber To provide sufficient air a suitable inlet should be provided into the room or space in which the boiler is situated the sizes of which are shown in Table 9 An air brick or other form of continuous air supply may have to be built into the installation in order to ensure an adequate supply of air 6 2 If the appliance is to be installed in a confined space or compartment two air...

Page 7: ...onal pump location Manual reset overheat thermostat Strain relief bush Burner plug in connector High limit thermostat Fire valve clip Side panel Top panel Front panel Thermostat knob Manual reset over heat thermostat phial Automatic reset high limit thermostat phial Control thermostat phial Split pin Control Box Assembly ...

Page 8: ...8 Fig 3 Room Sealed Balanced Flue Appliance RS ...

Page 9: ...and adjusted to achieve a flue draught within the specified range 7 2 Low Level Discharge LLD See Fig 5 The low level flue kit is not designed for use with this appliance as there is no provision for installation of the flue gas purge timer However where fume odour will not present a problem eg boilerhouse outhouse the flue kit may be used without the purge unit Alternatively a standard Danesmoor ...

Page 10: ...tension kit a Rear Discharge 4 to 7 Single Skin Wall For use with non standard single skin walls up to 182 mm thick Where noise emission from the flue terminal is likely to be of concern it is recommended that the standard 12 in terminal is used and the appliance stood away from the wall to take up the extra terminal body length c Rear Discharge Extension Kit 12 to 36 Wall X For use where the wall...

Page 11: ...ance of combustion products An alternative flue terminal position should be sought when there is any possibility of a nuisance being caused by inadequate dispersal of flue products Terminals should be positioned so as to avoid products of combustion entering into buildings Fig 7 Flue terminating positions for oil fired appliances Window Flue Terminal Fig 8 Terminal guard Minimum dimensions 265 280...

Page 12: ... the burner and the length of pipe run b The oil supply pipe should be laid as level as possible to avoid air pockets and unnecessary friction losses c The following components should be fitted in the fuel line between the storage tank and burner 1 A Manual isolating valve installed as close to the tank as possible 2 A fire valve in accordance with BS5410 as shown in Fig 10 The fire valve should b...

Page 13: ...level H 4 m 13 ft maximum Fire valve to BS 5410 Fire valve to BS 5410 Isolating valve Isolating valve Fire detection element Filter Burner Burner Wall Wall b Double pipe system Isolating valve Non return valve Non return valve Fire detection element Isolating valve Oil tank c Single pipe lift system with de aerator Fire valve to BS 5410 H 3 5 m 11 5 ft maximum Burner Wall Fire detection element De...

Page 14: ...14 Fig 11 Oil Pipe Installation Fig 12 Typical Open Vent Fully Pumped System Honeywell Y plan ...

Page 15: ...Domestic hot water cylinder Pressure gauge Safety valve To system filling device see Fig 14 Fig 14 System filling and make up Temporary hose Heating return Non return valve Stop cock Auto air vent Fill point Heating return 30mm 12in min above highest point of the system Make up vessel METHOD 1 METHOD 2 Boiler Automatic bypass valve to be fitted where thermostatic radiator valves are fitted on all ...

Page 16: ...em Pipework Copper pipework must be used when installing the appliance on a sealed system 2 General The system should be installed in compliance with the requirements of BS5449 Part 1 The boiler must be fitted with a spring loaded safety valve set to operate at 3 bar 45 psi and the pipe connections made throughout the system must be capable of sustaining a pressure of up to 3 bar The following is ...

Page 17: ... junction box remotely from the boiler it can be easily connected into the Worcester Utility Oil Boiler 10 WAY JUNCTION BOX NOTE If a frost thermostat is required it can be wired to the remote junction box NOTE The 10 way junction box must be a terminal block type and current rated to at least 5 amps Remote Pre wired Junction Box OUTSIDE BOILER INSIDE BOILER Live Neutral Earth Control Box Connecto...

Page 18: ... Never use soldered joints on oil supply pipes as this could cause a hazard in the case of a fire 2 Fit an isolating valve at the end of the oil line close to the burner and ensure that the valve is closed Continue from step 11 5 b 5 Room sealed balanced flue appliance a Single pipe suction lift with de aerator For connection of single pipe suction lift with de aerator follow the proceedure as for...

Page 19: ...sulation is positioned correctly in the bottom of the boiler 3 Check that all baffles are correctly located and the heat shield is correctly mounted 20 25 26 32 32 50 and 50 70 models only as shown in Fig 24 4 Check that the baffle retainer is correctly mounted 20 25 26 32 32 50 and 50 70 models only as shown in Fig 24c 24d and 24e 5 On the 50 70 remove and discard the transit baffle retainer as s...

Page 20: ...Check that the flue temperature does not exceed the value specified in Tables 2 to 8 If this is the case then check that the baffles are correctly located If the baffles are correctly located then reduce the pump pressure since nozzle variations of up to or 15 may occur 12 15 Remove the oil pressure gauge and manifold and check all oil system joints for any signs of leakage 12 16 On the RS balance...

Page 21: ...djustment Screw Adjusting disc To adjust the nozzle position undo the locking screw located at the rear of the nozzle line and rotate the adjusting disc one turn anti clockwise to move forward by 1 mm Output Dimension kW Head Type A 15 PL 6 7 21 5 10 3 mm 17 PL 6 7 21 5 10 5 mm 19 PL 6 7 21 5 10 5 mm Fig 20 Electro Oil Inter B11 Burner 20 25 model Combustion Head Draught tube Nozzle Nozzle block S...

Page 22: ...zzle block Spark gap 2 5 3 0mm 0mm 7 5mm A Air guide Remove at 50kW 28sec only Nozzle block 0mm Nozzle 7 5mm Blast tube Spark gap 2 5 to 3mm A Fig 22 Electro Oil Inter B20C Burner 32 50 model Combustion Head PL 10 8 10 6 19 10 E x 78mm Output Fuel Dimension mm kW A 32 28sec Kerosene 3 41 28sec Kerosene 6 50 28sec Kerosene 6 41 35sec Gas Oil 6 50 35sec Gas Oil 6 ...

Page 23: ... and clean the air intake ducts at the rear and underneath the boiler and the air intake grille at the end of the terminal 5 Check and clean the baffle retainer 20 25 26 32 32 50 and 50 70 models 6 Check and clean the cap retainer 32 50 and 50 70 models 7 Check and clean the baffles 8 Check and clean the heat exchanger surface 9 Check the heat shield 20 25 26 32 32 50 and 50 70 models 10 Check the...

Page 24: ... the electrical box d Feed the electrical lead back through the grommet seal to give sufficient play to allow withdrawal and inspection of the burner e Slacken the two M6 burner locking screws using a 5mm Allen key and remove the burner b 15 19 c 20 25 and 26 32 ENSURE THAT ALL BAFFLES ARE SEATED IN POSITION a 12 14 Baffle retainer Baffle Baffle Heat shield Fig 24 Location of Boiler Flueway Baffle...

Page 25: ...ear of any debris and clean if necessary d Check that the 3 holes in the check valve are clear of any debris Discard the check valve if the holes cannot be cleared or if the unit is defective and replace with a new one e Replace in the reverse order 5 It is strongly recommended that the oil atomising nozzle is replaced at each service If this is not possible then remove and clean the integral filt...

Page 26: ...o compress the gasket and tighten the two locking screws using a 5mm Allen key Note It is important that a good seal is made between the burner and the boiler to prevent re emission of the flue gases from the combustion chamber to the burner inlet or the room in the case of a CF LLD appliance 3 On the RS balanced flue model feed the electrical lead back through the hole in the burner surround hous...

Page 27: ...oiler does not respond to a call for heat Boiler thermostat faulty Check by linking out high limit and control thermostats Programmer open circuit Faulty control box Replace if necessary Flue draught incorrect Check flue draught Combustion settings incorrect Set up as in installation instructions Faulty nozzle Replace nozzle HIGH SMOKE NUMBER Faulty nozzle Replace nozzle Incorrect combustion setti...

Page 28: ...ovement All goods sold are subject to our official Conditions of Sale a copy of which may be obtained on application 8 716 114 746a 11 07 Bosch Group Worcester Bosch Group Cotswold Way Warndon Worcester WR4 9SW Telephone 01905 754624 Fax 01905 753130 Technical Helpline 08705 266241 Worcester Bosch Group is a trading name of BBT Thermotechnology UK Limited www worcester bosch co uk ...

Reviews: