Bosch WORCESTER DANESMOOR UTILITY 12/14 Installation And Servicing Instructions Download Page 16

The heating and hot water system must be provided in accor-
dance with the current Building Regulations.

9.1 

The appliance is suitable for connection to all conventional

indirect hot water systems utilising an indirect double feed cylinder. 

9.2 

The flow and return sockets are located at the rear of the

appliance, two at high level (flow) and two at low level (return).
Connection of the flow and return sockets can either be made on
diagonally opposite sockets or on the same side of the boiler.

9.3 

Provision has been made for locating the circulating pump

within the appliance cabinet. If required, the socket located in
the top front of the boiler should be used and the flow pipe run
either side of the boiler (See Figs. 2 and 3).

9.4 

On new installations it is recommended a room thermostat

or programmable room thermostat is used in the main zone and
thermostatic radiator valves are used in further heating zones.
On existing systems where a room thermostat is already fitted it
is recommended to fit thermostatic radiator valves at least in the
sleeping zones.
A automatic system bypass should be fitted on heating systems
when all of the radiators are fitted with thermostatic radiator valves.

9.5 

The pressure jet burner fitted to the appliance has full

automatic control and hence there is no requirement for heat
leak radiators.

9.6 

Any unused boiler tappings should be plugged prior to

filling. It should be noted that the flow tapping on the front of the
boiler requires plugging when not used.

9.7 

The primary system should be flushed and treated in

accordance with the recommendations of BS 7593 before the
system is handed over to the user.

9.8 

The pump should be set in accordance with the heating load

requirements to give a flow and return differential temperature
of 11°C under full load conditions.

Open Vent Primary System 

(See Fig. 12).

The following points are for guidance only. The system installation
should be carried out in accordance with BS 5449: Part 1.

1. 

System Pipework

The first metre of pipework from all appliance connections must be
in copper; afterwards copper or plastic pipe can be used. The
plastic pipe must be manufactued to BS 7291 and installed to BS
5955 part 8. It is important to protect the system components; the
plastic pipe specified must be resistant to the ingress of oxygen.

2. 

Feed and Expansion System

The feed and expansion pipes must rise continuously from the
appliance and must be of the minimum diameter shown in
Fig. 12.
The cistern must be arranged to provide a minimum static head of
1 metre above the top of the highest point in the heating circuit.

3. 

Filling and Venting

Air in the appliance is expelled through the vent pipe or
dissipated into the system. Manual air vents should be fitted at
any high points in the system.

Sealed Primary System 

(See Figs. 13 and 14).

The appliance is supplied with a manual reset high limit thermostat
and may therefore be fitted to a sealed heating system.

1. 

System Pipework

Copper pipework must be used when installing the appliance on
a sealed system.

2.

General

The system should be installed in compliance with the
requirements of BS5449: Part 1. The boiler must be fitted with a
spring loaded safety valve set to operate at 3 bar (45 psi) and the
pipe connections made throughout the system must be capable
of sustaining a pressure of up to 3 bar.
The following is a list of major items which must be fitted to the
system:

1. Safety valve – 3 bar
2. Pressure gauge – 0 to 4 bar.
3. Expansion vessel
4.   Automatic air vent

.

(See Fig. 15).

10.1 

The wiring between the appliance and the electrical supply

shall comply with current IEE wiring regulations (and any local
regulations which apply) for fixed wiring to a stationary appliance.

NOTE:

It must be possible to completely isolate the appliance.

10.2 

To gain access to the electrical terminal strip.

1. Isolate the mains electrical supply.
2. Remove the cabinet front panel by pulling forwards to

release the ball studs.

3. Pull the thermostat control knob forwards to remove from

its spindle.

4. Undo the facia retaining screws and remove the plate.

10.3 Mains Wiring
Mains supply - 230V AC ~ 50 Hz 5A External Fuse to
BS1362.

LIVE - Brown, NEUTRAL - Blue, EARTH - Green/Yellow
Mains Cable: 0.75mm

2

(24 x 0.20mm) to BS 6500 Table 16.

The supply to the boiler must be the only electrical supply to the
system. This ensures the safety of a single fused supply.
The mains supply cable should be connected into the terminals
marked 

(Live), 

N

(Neutral) and 

(Earth) on the appliance

terminal strip and securely held in the cable clamp located in the
right-hand side of the electrical tray base. To secure the cable,
remove the clamp retaining screw and pull its inner body out to
allow the cable to be fed through. With the cable in position refit
the screw and fully tighten to grip the cable. Feed the cable
between the side panel and the boiler insulation jacket and route
to the connection point avoiding any hot surfaces.
The appliance must be earthed.

10.4 Programmer 

A time clock or programmer may be added to the control system. A
two channel programmer will allow independent control of the central
heating and hot water. 

NOTE:

Under no circumstances should the timer be connected to

a separate electrical supply. Safety is assured from a single fused
supply to the boiler.

10.5 Safety Check

In the event of an electrical fault after the installation of the
appliance, the electrical system shall be checked for short
circuits, fuse failure or incorrect polarity of connections.

10.6 Pre-wired Remote Y Plan or S Plan System

(See Fig.16).
If the system is fully pre-wired at a junction box remotely from
the boiler it can be connected to the boiler. The diagram shows-
connection details of two popular proprietary systems
(Honeywell and Invensys), for these and other systems from
other manufacturers always use the boiler instructions in con-
junction with the system instructions.

10.7 Frost Protection 

For full frost protection a frost thermostat should be fitted so
that both the boiler and the circulating pump circuits are
energised under frost conditions. 

10. Electrical

9. Heating And Hot Water System

16

Summary of Contents for WORCESTER DANESMOOR UTILITY 12/14

Page 1: ...D ROOM SEALED BF FLOOR STANDING OIL FIRED PRESSURE JET APPLIANCES INSTALLATION AND SERVICING INSTRUCTIONS THESE INSTRUCTIONS ARE TO BE LEFT WITH THE APPLIANCE This appliance must be installed and serviced by a competent person Worcester supports the Benchmark code of practice ...

Page 2: ...ccording to the manufacturers instructions Without the completion of the Log book manufacturers may refuse to respond to a call out from a householder who will be advised that he or she must call back the installer who has not fulfilled his obligations to record the information required by the initiative It is important that The services and the system are properly flushed as specified The User is...

Page 3: ... mbar 66mbar 195mbar 3 mbar 6 mbar 12 mbar 19 mbar 7mbar 10mbar 24 g hr 35 kg hr 43 kg hr 57 kg hr 85 kg hr 115 kg hr 55 C minimum cut in o 82 C maximum cut out 5 C 100 0 6 C 110 0 6 C CF RS Model POWER SUPPLY HEATING FLOW HEATING RETURN MINIMUM FLUE REQUIREMENT Balanced Flue Kit Balanced Flue Kit Balanced Flue Kit Balanced Flue Kit Section 7 3 Section 7 3 Section 7 3 Section 7 3 N A N A 12 14 15 ...

Page 4: ...0 25 85 000 NOMINAL BOILER RATING AT NORMAL OPERATING TEMPERATURE 20 25 Table 4 Electro Oil Inter B11C Burner See Fig 20 Fuel Nozzle Pump Pressure p s i Fuel Flow Rate Flue Gas Temp C CO2 Approx Air Setting Appliance Input kW Btu hr kW Btu hr Output Kg h l h 28 Sec Kerosene 0 85 80 EH 110 2 36 2 99 225 11 0 11 5 11 28 5 97 000 26 89 000 28 Sec Kerosene 0 85 80 EH 130 2 66 3 37 240 11 0 11 5 12 32 ...

Page 5: ...2 0 12 5 2 75 45 3 154 500 41 140 000 28 Sec Kerosene 1 35 60 S 150 4 6 5 81 220 12 0 12 5 4 75 55 25 188 500 50 171 000 35 Sec Gas Oil 0 85 60 S 210 3 82 4 6 190 12 0 12 5 2 75 45 3 154 500 41 140 000 35 Sec Gas Oil 1 0 60 S 260 4 66 5 61 210 12 5 13 0 6 5 55 25 188 500 50 171 000 NOMINAL BOILER RATING AT NORMAL OPERATING TEMPERATURE 32 50 Table 7 Electro Oil Inter B20C Burner See Fig 22 Conventi...

Page 6: ...e combustion chamber To provide sufficient air a suitable inlet should be provided into the room or space in which the boiler is situated the sizes of which are shown in Table 9 An air brick or other form of continuous air supply may have to be built into the installation in order to ensure an adequate supply of air 6 2 If the appliance is to be installed in a confined space or compartment two air...

Page 7: ...onal pump location Manual reset overheat thermostat Strain relief bush Burner plug in connector High limit thermostat Fire valve clip Side panel Top panel Front panel Thermostat knob Manual reset over heat thermostat phial Automatic reset high limit thermostat phial Control thermostat phial Split pin Control Box Assembly ...

Page 8: ...8 Fig 3 Room Sealed Balanced Flue Appliance RS ...

Page 9: ...and adjusted to achieve a flue draught within the specified range 7 2 Low Level Discharge LLD See Fig 5 The low level flue kit is not designed for use with this appliance as there is no provision for installation of the flue gas purge timer However where fume odour will not present a problem eg boilerhouse outhouse the flue kit may be used without the purge unit Alternatively a standard Danesmoor ...

Page 10: ...tension kit a Rear Discharge 4 to 7 Single Skin Wall For use with non standard single skin walls up to 182 mm thick Where noise emission from the flue terminal is likely to be of concern it is recommended that the standard 12 in terminal is used and the appliance stood away from the wall to take up the extra terminal body length c Rear Discharge Extension Kit 12 to 36 Wall X For use where the wall...

Page 11: ...ance of combustion products An alternative flue terminal position should be sought when there is any possibility of a nuisance being caused by inadequate dispersal of flue products Terminals should be positioned so as to avoid products of combustion entering into buildings Fig 7 Flue terminating positions for oil fired appliances Window Flue Terminal Fig 8 Terminal guard Minimum dimensions 265 280...

Page 12: ... the burner and the length of pipe run b The oil supply pipe should be laid as level as possible to avoid air pockets and unnecessary friction losses c The following components should be fitted in the fuel line between the storage tank and burner 1 A Manual isolating valve installed as close to the tank as possible 2 A fire valve in accordance with BS5410 as shown in Fig 10 The fire valve should b...

Page 13: ...level H 4 m 13 ft maximum Fire valve to BS 5410 Fire valve to BS 5410 Isolating valve Isolating valve Fire detection element Filter Burner Burner Wall Wall b Double pipe system Isolating valve Non return valve Non return valve Fire detection element Isolating valve Oil tank c Single pipe lift system with de aerator Fire valve to BS 5410 H 3 5 m 11 5 ft maximum Burner Wall Fire detection element De...

Page 14: ...14 Fig 11 Oil Pipe Installation Fig 12 Typical Open Vent Fully Pumped System Honeywell Y plan ...

Page 15: ...Domestic hot water cylinder Pressure gauge Safety valve To system filling device see Fig 14 Fig 14 System filling and make up Temporary hose Heating return Non return valve Stop cock Auto air vent Fill point Heating return 30mm 12in min above highest point of the system Make up vessel METHOD 1 METHOD 2 Boiler Automatic bypass valve to be fitted where thermostatic radiator valves are fitted on all ...

Page 16: ...em Pipework Copper pipework must be used when installing the appliance on a sealed system 2 General The system should be installed in compliance with the requirements of BS5449 Part 1 The boiler must be fitted with a spring loaded safety valve set to operate at 3 bar 45 psi and the pipe connections made throughout the system must be capable of sustaining a pressure of up to 3 bar The following is ...

Page 17: ... junction box remotely from the boiler it can be easily connected into the Worcester Utility Oil Boiler 10 WAY JUNCTION BOX NOTE If a frost thermostat is required it can be wired to the remote junction box NOTE The 10 way junction box must be a terminal block type and current rated to at least 5 amps Remote Pre wired Junction Box OUTSIDE BOILER INSIDE BOILER Live Neutral Earth Control Box Connecto...

Page 18: ... Never use soldered joints on oil supply pipes as this could cause a hazard in the case of a fire 2 Fit an isolating valve at the end of the oil line close to the burner and ensure that the valve is closed Continue from step 11 5 b 5 Room sealed balanced flue appliance a Single pipe suction lift with de aerator For connection of single pipe suction lift with de aerator follow the proceedure as for...

Page 19: ...sulation is positioned correctly in the bottom of the boiler 3 Check that all baffles are correctly located and the heat shield is correctly mounted 20 25 26 32 32 50 and 50 70 models only as shown in Fig 24 4 Check that the baffle retainer is correctly mounted 20 25 26 32 32 50 and 50 70 models only as shown in Fig 24c 24d and 24e 5 On the 50 70 remove and discard the transit baffle retainer as s...

Page 20: ...Check that the flue temperature does not exceed the value specified in Tables 2 to 8 If this is the case then check that the baffles are correctly located If the baffles are correctly located then reduce the pump pressure since nozzle variations of up to or 15 may occur 12 15 Remove the oil pressure gauge and manifold and check all oil system joints for any signs of leakage 12 16 On the RS balance...

Page 21: ...djustment Screw Adjusting disc To adjust the nozzle position undo the locking screw located at the rear of the nozzle line and rotate the adjusting disc one turn anti clockwise to move forward by 1 mm Output Dimension kW Head Type A 15 PL 6 7 21 5 10 3 mm 17 PL 6 7 21 5 10 5 mm 19 PL 6 7 21 5 10 5 mm Fig 20 Electro Oil Inter B11 Burner 20 25 model Combustion Head Draught tube Nozzle Nozzle block S...

Page 22: ...zzle block Spark gap 2 5 3 0mm 0mm 7 5mm A Air guide Remove at 50kW 28sec only Nozzle block 0mm Nozzle 7 5mm Blast tube Spark gap 2 5 to 3mm A Fig 22 Electro Oil Inter B20C Burner 32 50 model Combustion Head PL 10 8 10 6 19 10 E x 78mm Output Fuel Dimension mm kW A 32 28sec Kerosene 3 41 28sec Kerosene 6 50 28sec Kerosene 6 41 35sec Gas Oil 6 50 35sec Gas Oil 6 ...

Page 23: ... and clean the air intake ducts at the rear and underneath the boiler and the air intake grille at the end of the terminal 5 Check and clean the baffle retainer 20 25 26 32 32 50 and 50 70 models 6 Check and clean the cap retainer 32 50 and 50 70 models 7 Check and clean the baffles 8 Check and clean the heat exchanger surface 9 Check the heat shield 20 25 26 32 32 50 and 50 70 models 10 Check the...

Page 24: ... the electrical box d Feed the electrical lead back through the grommet seal to give sufficient play to allow withdrawal and inspection of the burner e Slacken the two M6 burner locking screws using a 5mm Allen key and remove the burner b 15 19 c 20 25 and 26 32 ENSURE THAT ALL BAFFLES ARE SEATED IN POSITION a 12 14 Baffle retainer Baffle Baffle Heat shield Fig 24 Location of Boiler Flueway Baffle...

Page 25: ...ear of any debris and clean if necessary d Check that the 3 holes in the check valve are clear of any debris Discard the check valve if the holes cannot be cleared or if the unit is defective and replace with a new one e Replace in the reverse order 5 It is strongly recommended that the oil atomising nozzle is replaced at each service If this is not possible then remove and clean the integral filt...

Page 26: ...o compress the gasket and tighten the two locking screws using a 5mm Allen key Note It is important that a good seal is made between the burner and the boiler to prevent re emission of the flue gases from the combustion chamber to the burner inlet or the room in the case of a CF LLD appliance 3 On the RS balanced flue model feed the electrical lead back through the hole in the burner surround hous...

Page 27: ...oiler does not respond to a call for heat Boiler thermostat faulty Check by linking out high limit and control thermostats Programmer open circuit Faulty control box Replace if necessary Flue draught incorrect Check flue draught Combustion settings incorrect Set up as in installation instructions Faulty nozzle Replace nozzle HIGH SMOKE NUMBER Faulty nozzle Replace nozzle Incorrect combustion setti...

Page 28: ...ovement All goods sold are subject to our official Conditions of Sale a copy of which may be obtained on application 8 716 114 746a 11 07 Bosch Group Worcester Bosch Group Cotswold Way Warndon Worcester WR4 9SW Telephone 01905 754624 Fax 01905 753130 Technical Helpline 08705 266241 Worcester Bosch Group is a trading name of BBT Thermotechnology UK Limited www worcester bosch co uk ...

Reviews: