background image

14.6 Clean the Boiler
1. 

Remove the boiler top access door by releasing the M10 nuts

and check the fibreglass rope seal. Replace the seal if necessary.

2.

Remove the burner mounting flange by releasing the three

M10 nuts and check the fibre glass gasket, it is imperative that
this seal is in good condition. Replace the seal if necessary
(32/50 and 50/70 models only).

3. 

Remove and check the baffle retainer, where fitted (20/25,

26/32, 32/50 and 50/70 models). See Fig. 24.

4. 

Remove the baffles, clean and check their condition. Replace

any baffles considered to be badly corroded.

5. 

Remove and check the cap retainer, where fitted (32/50 and

50/70 models only). See Fig. 24d, 24e & 25.

6. 

Remove the cap (32/50 and 50/70 models only) and check

the ‘rocksulate’ gasket. Replace the seal if necessary.

7. 

Thoroughly clean all of the heat exchanger surfaces using a stiff

wire brush and vacuum clean all loose debris from the combustion
chamber. Take care not to damage the base insulation!

8. 

Remove and check the heat shield where fitted (20/25,

26/32, 32/50 and 50/70 models). (See Fig. 24).

9. 

Check the combustion chamber base insulation board and

replace if there is any sign of damage.

10. 

Check and clean the flue.

11. 

Replace the items in reverse order noting the baffle positions

shown in Fig. 24.

14.7 Fire Valve.

Check that a fire valve is fitted to the incoming oil line with the
body located outside the premises and the detection element

located within the appliance case. A fire valve clip is provided
for this purpose as shown in Figs 2 & 3. Test the operation of the
fire valve to ensure that the mechanism operates and that the oil
supply is completely isolated.

NOTE:

The fire sensing element must be located on the top face of

the burner surround box on RS balanced flue models, as shown
in Fig.3, to allow quick detection of a dangerous situation.

14.8 Recommission the Burner.
1. 

Connect the flexible oil supply hose to the isolating valve and

tighten sufficiently to form a good seal. Where a double pipe
system is being used connect the oil return flexible hose to
return pipe fitting.

2. 

With the sponge O-ring gasket around the burner blast tube

insert the burner into the housing tube. Push the burner firmly
forward to compress the gasket and tighten the two locking
screws, using a 5mm Allen key.

Note: 

It is important that a good seal is made between the

burner and the boiler to prevent re-emission of the flue gases
from the combustion chamber to the burner inlet, or the room in
the case of a CF/LLD appliance.

3. 

On the RS balanced flue model feed the electrical lead back

through the hole in the burner surround housing (in the reverse
order to that described in 11.2) and fit the grommet into the hole
ensuring a seal is made.

4. 

Reconnect the electrical lead plug into the control box.

5. 

Turn on the oil supply at the service cock.

6. 

Recommission the burner as described in Section 12.

26

15. Short Parts List

Part

Manufacturers Reference

Qty

Worcester Part No.

Burner for 12/14

Bentone B9A

1

8 716 104 431 0

B9A Combustion Head

PL 6/7/21.5/10-E x 78mm

1

8 716 157 041 0

Burner for 15/19

Bentone B9B

1

8 716 142 705 0

B9B combustion Head

PL 6/7/21.5/10 x 78mm

1

8 716 156 697 0

Burner for 20/25

Bentone B11C

1

8 716 104 432 0

B11C Combustion Head

PL 10/4/24/10 x 78mm

1

8 716 142 784 0

Burner for 26/32

Bentone Sterling 40

1

8 716 142 700 0

Sterling 40 Combustion Head

PL 6/7/21.5/10 x 78mm

1

8 716 156 697 0

Burner for 32/50

Bentone B20C

1

8 716 104 546 0

B20C Combustion Head

PL10/8/10/6/19/10-E x 78mm

1

8 716 104 769 0

Burner for 50/70

Bentone B20B

1

8 716 104 547 0

B20B Break Plate

PL 21.5/10 (type K)

1

8 716 156 518 0

B20B Blast Tube

Type K x 94mm

1

8 716 142 739 0

Burner control 1.

Control Box

Satronic TF 832.3

1

8 716 156 648 0

B9, B11 and B20

Photocell

Satronic MZ770

1

8 716 142 735 0

Sterling 40

Photocell

Satronic MZ770

1

8 716 156 692 0

Control Box Base

Satronic S01 S701

1

8 716 142 782 0

Ignition Electrode

1

8 716 142 752 0

Motor B9

AEG or Simel 70 W

1

8 716 156 597 0

Motor B11 and B20

AEG (FHP) 90W

1

8 716 142 732 0

Motor Sterling 40

AEG (FHP) 90W

1

8 716 156 645 0

Oil Pump B9

Danfoss BFP41L3

1

8 716 142 743 0

Oil Pump (B11, B20 and Sterling 40)

Danfoss BFP11L3

1

8 716 142 736 0

Transformer

Danfoss EBI 052F0030 (excludes cable)

1

8 716 156 696 0

Mechanical Shut-Off Valve

1

8 716 156 658 0

Flexible Oil Line Kit

Worcester

1

8 716 156 663 0

Burner 'O' Shaped Gasket

Worcester

1

8 716 140 902 0

Control Thermostat 

Siebe K36-P2312

1

8 716 142 309 0

Automatic Reset High Limit Thermostat

Siebe LO7-P1022

1

8 716 142 311 0

Manual Reset High Limit Thermostat

Siebe LM7-P5075

1

8 716 142 310 0

Summary of Contents for WORCESTER DANESMOOR UTILITY 12/14

Page 1: ...D ROOM SEALED BF FLOOR STANDING OIL FIRED PRESSURE JET APPLIANCES INSTALLATION AND SERVICING INSTRUCTIONS THESE INSTRUCTIONS ARE TO BE LEFT WITH THE APPLIANCE This appliance must be installed and serviced by a competent person Worcester supports the Benchmark code of practice ...

Page 2: ...ccording to the manufacturers instructions Without the completion of the Log book manufacturers may refuse to respond to a call out from a householder who will be advised that he or she must call back the installer who has not fulfilled his obligations to record the information required by the initiative It is important that The services and the system are properly flushed as specified The User is...

Page 3: ... mbar 66mbar 195mbar 3 mbar 6 mbar 12 mbar 19 mbar 7mbar 10mbar 24 g hr 35 kg hr 43 kg hr 57 kg hr 85 kg hr 115 kg hr 55 C minimum cut in o 82 C maximum cut out 5 C 100 0 6 C 110 0 6 C CF RS Model POWER SUPPLY HEATING FLOW HEATING RETURN MINIMUM FLUE REQUIREMENT Balanced Flue Kit Balanced Flue Kit Balanced Flue Kit Balanced Flue Kit Section 7 3 Section 7 3 Section 7 3 Section 7 3 N A N A 12 14 15 ...

Page 4: ...0 25 85 000 NOMINAL BOILER RATING AT NORMAL OPERATING TEMPERATURE 20 25 Table 4 Electro Oil Inter B11C Burner See Fig 20 Fuel Nozzle Pump Pressure p s i Fuel Flow Rate Flue Gas Temp C CO2 Approx Air Setting Appliance Input kW Btu hr kW Btu hr Output Kg h l h 28 Sec Kerosene 0 85 80 EH 110 2 36 2 99 225 11 0 11 5 11 28 5 97 000 26 89 000 28 Sec Kerosene 0 85 80 EH 130 2 66 3 37 240 11 0 11 5 12 32 ...

Page 5: ...2 0 12 5 2 75 45 3 154 500 41 140 000 28 Sec Kerosene 1 35 60 S 150 4 6 5 81 220 12 0 12 5 4 75 55 25 188 500 50 171 000 35 Sec Gas Oil 0 85 60 S 210 3 82 4 6 190 12 0 12 5 2 75 45 3 154 500 41 140 000 35 Sec Gas Oil 1 0 60 S 260 4 66 5 61 210 12 5 13 0 6 5 55 25 188 500 50 171 000 NOMINAL BOILER RATING AT NORMAL OPERATING TEMPERATURE 32 50 Table 7 Electro Oil Inter B20C Burner See Fig 22 Conventi...

Page 6: ...e combustion chamber To provide sufficient air a suitable inlet should be provided into the room or space in which the boiler is situated the sizes of which are shown in Table 9 An air brick or other form of continuous air supply may have to be built into the installation in order to ensure an adequate supply of air 6 2 If the appliance is to be installed in a confined space or compartment two air...

Page 7: ...onal pump location Manual reset overheat thermostat Strain relief bush Burner plug in connector High limit thermostat Fire valve clip Side panel Top panel Front panel Thermostat knob Manual reset over heat thermostat phial Automatic reset high limit thermostat phial Control thermostat phial Split pin Control Box Assembly ...

Page 8: ...8 Fig 3 Room Sealed Balanced Flue Appliance RS ...

Page 9: ...and adjusted to achieve a flue draught within the specified range 7 2 Low Level Discharge LLD See Fig 5 The low level flue kit is not designed for use with this appliance as there is no provision for installation of the flue gas purge timer However where fume odour will not present a problem eg boilerhouse outhouse the flue kit may be used without the purge unit Alternatively a standard Danesmoor ...

Page 10: ...tension kit a Rear Discharge 4 to 7 Single Skin Wall For use with non standard single skin walls up to 182 mm thick Where noise emission from the flue terminal is likely to be of concern it is recommended that the standard 12 in terminal is used and the appliance stood away from the wall to take up the extra terminal body length c Rear Discharge Extension Kit 12 to 36 Wall X For use where the wall...

Page 11: ...ance of combustion products An alternative flue terminal position should be sought when there is any possibility of a nuisance being caused by inadequate dispersal of flue products Terminals should be positioned so as to avoid products of combustion entering into buildings Fig 7 Flue terminating positions for oil fired appliances Window Flue Terminal Fig 8 Terminal guard Minimum dimensions 265 280...

Page 12: ... the burner and the length of pipe run b The oil supply pipe should be laid as level as possible to avoid air pockets and unnecessary friction losses c The following components should be fitted in the fuel line between the storage tank and burner 1 A Manual isolating valve installed as close to the tank as possible 2 A fire valve in accordance with BS5410 as shown in Fig 10 The fire valve should b...

Page 13: ...level H 4 m 13 ft maximum Fire valve to BS 5410 Fire valve to BS 5410 Isolating valve Isolating valve Fire detection element Filter Burner Burner Wall Wall b Double pipe system Isolating valve Non return valve Non return valve Fire detection element Isolating valve Oil tank c Single pipe lift system with de aerator Fire valve to BS 5410 H 3 5 m 11 5 ft maximum Burner Wall Fire detection element De...

Page 14: ...14 Fig 11 Oil Pipe Installation Fig 12 Typical Open Vent Fully Pumped System Honeywell Y plan ...

Page 15: ...Domestic hot water cylinder Pressure gauge Safety valve To system filling device see Fig 14 Fig 14 System filling and make up Temporary hose Heating return Non return valve Stop cock Auto air vent Fill point Heating return 30mm 12in min above highest point of the system Make up vessel METHOD 1 METHOD 2 Boiler Automatic bypass valve to be fitted where thermostatic radiator valves are fitted on all ...

Page 16: ...em Pipework Copper pipework must be used when installing the appliance on a sealed system 2 General The system should be installed in compliance with the requirements of BS5449 Part 1 The boiler must be fitted with a spring loaded safety valve set to operate at 3 bar 45 psi and the pipe connections made throughout the system must be capable of sustaining a pressure of up to 3 bar The following is ...

Page 17: ... junction box remotely from the boiler it can be easily connected into the Worcester Utility Oil Boiler 10 WAY JUNCTION BOX NOTE If a frost thermostat is required it can be wired to the remote junction box NOTE The 10 way junction box must be a terminal block type and current rated to at least 5 amps Remote Pre wired Junction Box OUTSIDE BOILER INSIDE BOILER Live Neutral Earth Control Box Connecto...

Page 18: ... Never use soldered joints on oil supply pipes as this could cause a hazard in the case of a fire 2 Fit an isolating valve at the end of the oil line close to the burner and ensure that the valve is closed Continue from step 11 5 b 5 Room sealed balanced flue appliance a Single pipe suction lift with de aerator For connection of single pipe suction lift with de aerator follow the proceedure as for...

Page 19: ...sulation is positioned correctly in the bottom of the boiler 3 Check that all baffles are correctly located and the heat shield is correctly mounted 20 25 26 32 32 50 and 50 70 models only as shown in Fig 24 4 Check that the baffle retainer is correctly mounted 20 25 26 32 32 50 and 50 70 models only as shown in Fig 24c 24d and 24e 5 On the 50 70 remove and discard the transit baffle retainer as s...

Page 20: ...Check that the flue temperature does not exceed the value specified in Tables 2 to 8 If this is the case then check that the baffles are correctly located If the baffles are correctly located then reduce the pump pressure since nozzle variations of up to or 15 may occur 12 15 Remove the oil pressure gauge and manifold and check all oil system joints for any signs of leakage 12 16 On the RS balance...

Page 21: ...djustment Screw Adjusting disc To adjust the nozzle position undo the locking screw located at the rear of the nozzle line and rotate the adjusting disc one turn anti clockwise to move forward by 1 mm Output Dimension kW Head Type A 15 PL 6 7 21 5 10 3 mm 17 PL 6 7 21 5 10 5 mm 19 PL 6 7 21 5 10 5 mm Fig 20 Electro Oil Inter B11 Burner 20 25 model Combustion Head Draught tube Nozzle Nozzle block S...

Page 22: ...zzle block Spark gap 2 5 3 0mm 0mm 7 5mm A Air guide Remove at 50kW 28sec only Nozzle block 0mm Nozzle 7 5mm Blast tube Spark gap 2 5 to 3mm A Fig 22 Electro Oil Inter B20C Burner 32 50 model Combustion Head PL 10 8 10 6 19 10 E x 78mm Output Fuel Dimension mm kW A 32 28sec Kerosene 3 41 28sec Kerosene 6 50 28sec Kerosene 6 41 35sec Gas Oil 6 50 35sec Gas Oil 6 ...

Page 23: ... and clean the air intake ducts at the rear and underneath the boiler and the air intake grille at the end of the terminal 5 Check and clean the baffle retainer 20 25 26 32 32 50 and 50 70 models 6 Check and clean the cap retainer 32 50 and 50 70 models 7 Check and clean the baffles 8 Check and clean the heat exchanger surface 9 Check the heat shield 20 25 26 32 32 50 and 50 70 models 10 Check the...

Page 24: ... the electrical box d Feed the electrical lead back through the grommet seal to give sufficient play to allow withdrawal and inspection of the burner e Slacken the two M6 burner locking screws using a 5mm Allen key and remove the burner b 15 19 c 20 25 and 26 32 ENSURE THAT ALL BAFFLES ARE SEATED IN POSITION a 12 14 Baffle retainer Baffle Baffle Heat shield Fig 24 Location of Boiler Flueway Baffle...

Page 25: ...ear of any debris and clean if necessary d Check that the 3 holes in the check valve are clear of any debris Discard the check valve if the holes cannot be cleared or if the unit is defective and replace with a new one e Replace in the reverse order 5 It is strongly recommended that the oil atomising nozzle is replaced at each service If this is not possible then remove and clean the integral filt...

Page 26: ...o compress the gasket and tighten the two locking screws using a 5mm Allen key Note It is important that a good seal is made between the burner and the boiler to prevent re emission of the flue gases from the combustion chamber to the burner inlet or the room in the case of a CF LLD appliance 3 On the RS balanced flue model feed the electrical lead back through the hole in the burner surround hous...

Page 27: ...oiler does not respond to a call for heat Boiler thermostat faulty Check by linking out high limit and control thermostats Programmer open circuit Faulty control box Replace if necessary Flue draught incorrect Check flue draught Combustion settings incorrect Set up as in installation instructions Faulty nozzle Replace nozzle HIGH SMOKE NUMBER Faulty nozzle Replace nozzle Incorrect combustion setti...

Page 28: ...ovement All goods sold are subject to our official Conditions of Sale a copy of which may be obtained on application 8 716 114 746a 11 07 Bosch Group Worcester Bosch Group Cotswold Way Warndon Worcester WR4 9SW Telephone 01905 754624 Fax 01905 753130 Technical Helpline 08705 266241 Worcester Bosch Group is a trading name of BBT Thermotechnology UK Limited www worcester bosch co uk ...

Reviews: