5
~NOTE
: At 70kW the air guide should be removed (See Fig. 23)
*
NOTE:
For use on conventional flue only.
**
NOTE:
The flue gas temperature is measured in the gas sampling hole on the flue outlet plate. The probe should be inserted to a depth of 50mm and angled towards the flue outlet.
The temperature measured is not an absolute flue gas temperature and is for general guidance purposes only!
NOTE:
The pump pressure given is for general guidance only as variations in nozzle output can be up to ± 15%. It is, therefore, essential that the air is adjusted to give the correct CO
2
value.
NOTE:
The nozzle type used on 28 Sec. Kerosene outputs are nozzles calibrated specifically for use with 28 Sec. Kerosene which gives less variation in nozzle output than the standard
35 Sec. Gas Oil nozzles. However, if a 28 Sec. Kerosene nozzle is not available at servicing or commissioning it is appropriate to install a 35 Sec. Gas Oil nozzle providing the output, spray
angle and pattern of the nozzle is the same as the 28 Sec. Kerosene nozzle (e.g. 0.75 80°EH may be replaced with a 0.75 80°H).
28 Sec. Kerosene*
0.85 60°ES
160
2.94
3.72
165
12.0-12.5
1.0
35.4
121,000
32
109,000
28 Sec. Kerosene*
1.20 60°S
150
3.77
4.76
190
12.0-12.5
2.75
45.3
154,500
41
140,000
28 Sec. Kerosene*
1.35 60°S
150
4.6
5.81
220
12.0-12.5
4.75
55.25 188,500
50
171,000
35 Sec. Gas Oil*
0.85 60°S
210
3.82
4.6
190
12.0-12.5
2.75
45.3
154,500
41
140,000
35 Sec. Gas Oil*
1.0 60°S
260
4.66
5.61
210
12.5-13.0
6.5
55.25 188,500
50
171,000
NOMINAL BOILER RATING AT NORMAL OPERATING TEMPERATURE
32/50 Table 7. Electro Oil Inter B20C Burner
(See Fig. 22)
Conventional Flue Appliance (CF)
Fuel
Nozzle
Pump
Pressure
(p.s.i.)
Fuel Flow
Rate
Flue Gas
Temp.
(°C)**
%CO
2
Approx.
Air
Setting
Appliance
Input
kW
Btu/hr
kW
Btu/hr
Output
Kg/h
l/h
28 Sec. Kerosene*
1.35 60°S
175
4.62
5.85
195
11.5-12.0
2.75
55.5
190,000
50
171,000
28 Sec. Kerosene*
1.75 60°S
140
5.55
7.03
210
12.0-12.5
4
67
229,000
60
205,000
~28 Sec. Kerosene*
2.00 60°S
135
6.47
8.19
225
12.5-13.0
4.5
78
268,000
70
239,000
35 Sec. Gas Oil*
1.00 60°S
245
4.69
5.52
195
11.0-11.5
2.75
55.5
190,000
50
171,000
35 Sec. Gas Oil*
1.35 60°S
175
5.63
6.62
210
12.0-12.5
4
67
229,000
60
205,000
~35 Sec. Gas Oil*
1.35 60°S
245
6.57
7.73
225
12.5-13.0
4.5
78
268,000
70
239,000
NOMINAL BOILER RATING AT NORMAL OPERATING TEMPERATURE
50/70 Table 8. Electro Oil Inter B20B Burner
(See Fig. 23)
Conventional Flue Appliance (CF)
Fuel
Nozzle
Pump
Pressure
(p.s.i.)
Fuel Flow
Rate
Flue Gas
Temp.
(°C)**
%CO
2
Approx.
Air
Setting
Appliance
Input
kW
Btu/hr
kW
Btu/hr
Output
Kg/h
l/h
At 50kW 28sec. Kerosene the airguide should be removed (See Fig. 22 ).