1.
Start at the pattern’s expected boundary and walk across the pattern moving closer to
the detector. Set the adjustment as low as possible for proper catch performance.
2.
Adjust the Microwave Range Adjustment Potentiometer to as low a setting as possible for
proper catch performance.
Figure 6.1: Sensitivity settings
Callout * Description
1 * Alarm LED (blue, green, or red)
2 * Microwave Range Adjustment Potentiometer
3.
At each pass, observe the color on the Alarm LED (refer to the
Sensitivity settings
figure
above).
4.
Walk test from the opposite direction to determine the coverage pattern boundaries from
both sides.
5.
When walk test is completed, the detector returns to normal operation after 90 sec of
inactivity.