Operating voltage AC/DC
Operating current AC/DC
Max. switching capacity
42 V
100 mA
250 mW
B10d value RAFIX 22 FS
Electrics:
B10d = 5,000,000 (acc. to the manufacturer)
Assumption: B10d = 5 × B10d
Exclusion of failure at < 6050 cycles
Mechanics:
B10d = 250,000 (acc. to the manufacturer)
Assumption: B10d = 5 × B10d
Exclusion of failure at < 6050 cycles
Tab. 7-4: Technical data, E-STOP button
For information on the standards, please refer to
8 Standards
8.1 Standards used
Standard
Meaning
EN 61000-6-4
Generic standards - Emission standard (industrial environments)
EN 61000-6-2
Generic standards – Noise immunity (industrial environments)
EN 61558-2-6
Transformer for 24 V power supply unit, safe separation
EN 61131-2
24 V current supply requirements
ISO 13850
Safety of machinery, E-STOP - principles for design
EN 60664-1
Overvoltage category II
EN 60529
Degrees of protection (including housings and installation com-
partments)
EN 60068-2-6
Vibration test
EN 60068-2-27
Shock test
EN 60721-3-1 to 3
Classification of environmental conditions
UL 508
Industrial Control Equipment
Tab. 8-1: Standards used
E-STOP button - Standards
The E-STOP button is identified as safety component according to machinery di-
rective 2006/42/EC (annex V-10, E-STOP devices) by the vendor. The compliance
with the directive is proven by adherence to the following European standards:
●
IEC 60204-1 (Safety of machinery - Electrical equipment of machines)
Bosch Rexroth AG
Standards
Embedded Terminals with Profibus DP
Master
10/41
DOK-CONTRL-VEP*XX.5***-IT01-EN-P