Destruction of screw terminals, insufficient contact
and loss of UL certification if no copper wire is used
or due to wrong tightening torque.
NOTICE
Use only copper wire for wiring the connection terminals. Tighten the screws of the
screw terminals with the following torque:
Threads
Mounting torques
M2.5
0.4 Nm
M3
0.7 Nm
M4
1.4 Nm
M5
2.8 Nm
Fig.14-1: Mounting torques
14.2
Cleaning Notes
● Clean the screen at least once a week using an antistatic fabric or a cleansing agent
containing alcohol.
Dissolution of the foil surface as well as the display
seal by solvents or by high pressure cleaning devi‐
ces!
NOTICE
● Do not use any solvents (e. g. diluents)!
● Do not use compressed air, steam jet and high pressure cleaning devices!
14.3
Regular Maintenance Tasks
Include the following measures in the maintenance schedule:
● At least once a year, all plug and terminal connections of the components are to be
checked regarding proper tightness and possible damage.
● Make sure that cables are not broken or crushed.
● Damaged parts must be replaced immediately.
Risk of injury by rotating fan impeller!
DANGER
The fan impeller is not to be touched with the hands and may not come into contact
with other objects.