Bosch Security Systems | 2005-04 | 9922 141 10364en
Plena Voice Alarm System
| Basic System Manual | Operation
en
| 41
table 5.2: System fault indicators
Indicator
Description
Recommended action
Additional information
Processor reset
A processor reset is
detected.
Switch the voice alarm
controller off and on again.
See section 4.5.3.
Network
A network fault is detected.
Contact your dealer.
This fault should not occur,
since this type of supervision
is disabled (see section 4.5)
Call/EMG
In 1-channel mode:
The internal power amplifier
of the voice alarm controller
failed.
In 2-channel mode:
The external power amplifier
failed.
In 1-channel mode:
Switch the voice alarm
controller off and on again.
In 2-channel mode:
Switch the external power
amplifier off and on again.
Music/Spare
In 1-channel mode:
The external power amplifier
failed.
In 2-channel mode:
The internal power amplifier
failed.
In 1-channel mode:
Switch the external power
amplifier off and on again.
In 2- channel mode:
Switch the voice alarm
controller off and on again.
Ground short
A short-to-ground fault in the
loudspeaker line cabling is
detected.
Check all loudspeaker lines
for short-to-ground situations.
Input
An input contact fault is
detected.
Contact your dealer.
This fault should not occur,
since this type of supervision
is disabled (see section 4.5).
Mains
A mains power failure is
detected.
Check the mains power
connection of the voice alarm
controller and the mains
power availability.
See section 3.15.2 and
Battery
A back-up power failure is
detected.
Check the back-up power
supply connection of the
voice alarm controller and the
back-up power availability.
See section 3.15.3 and
Message
A message fault is detected.
Switch the voice alarm
controller off and on again.
See section 4.5.4.
EMG mic
A emergency microphone
fault is detected.
Check the emergency
microphone. If necessary,
replace it.
RCP
A remote control panel fault
is detected.
Contact your dealer.
This fault should not occur,
since this type of supervision
is disabled (see section 4.5).
Router
A router fault is detected.
Contact your dealer.
This fault should not occur,
since this type of supervision
is disabled (see section 4.5).