Bosch Security Systems | 2005-04 | 9922 141 10364en
Plena Voice Alarm System
| Basic System Manual | Configuration
en
| 28
4.5 Supervision
4.5.1
Introduction
If the
Supervision
switch (see figure 4.1) is in the
ON
position, supervision is enabled. If it is in the
OFF
position, supervision is disabled.
If the
Supervision
switch is in the
OFF
position, the
Disabled
indicator on the front panel of the voice alarm
controller is lit (see figure 4.2) to indicate that
supervision is switched off.
4.5.2
Overview
The supervised functions can be configured with a PC
and the configuration software. To basic systems, the
default settings apply (see table 4.2).
4.5.3
Processor supervision
If supervision is enabled (see section 4.5.1), the
processor of the voice alarm controller is supervised by
a watchdog. If the watchdog triggers, the
Processor
reset
indicator on the front panel of the voice alarm
controller is lit. Then, the program memory is checked
and the processor resumes operation within 10 seconds.
The indicator remains on until the fault is acknowledged
and reset.
Note
Supervision is only necessary for systems that
have to comply to the IEC60849 evacuation
standard. If the system does not have to comply
to this standard, leave the switch in the OFF
position.
figure 4.2: Disabled indicator
Processor reset
Network
Call/EMG
Music/Spare
Ground short
Input
Mains
Battery
Zone1
Zone2
Zone3
Zone4
Zone5
Zone6
Fault Indicators
A
B
Disabled
Message
EMG mic
RCP
Router
0 dB
-6dB
-20dB
table 4.2: Default supervision settings
Supervision of:
Default setting
Processor
On. See section 4.5.3.
Network
Off.
Messages
Line supervision
On. See section 4.5.5.
Emergency microphone
On. See section 4.5.6.
Input contacts
Off.
Mains power
On. See section 4.5.7.
Battery power
On. See section 4.5.8.
Internal power amplifier
On. See section 4.5.9.
VOX 20 kHz input
Off.
External power amplifier
Depends on position of
the 2ch operation switch.
Note