Product Information Optical Smoke Detector NOM/NOM K 100 LSN
Seite 17 von 30
BDL
−
F.01U.002.709
A5.en / 29.12.2004
ST
−
FIR/ PRM1 / deh
6.5. Detector Fault
6.5.1. Detector exchange required/detectors highly contaminated
Time
Current
0%
30%
60%
80%
Fault
Exchange
Fault
Quiescent state value
Slight
contamination
100%
1
3
4
2
1
2
3
4
If there is contamination, the flow through the
photo cell increases
A message may be transmitted if the
30% threshold is reached in 16 consecutive contamination
measurements. The detector alarm threshold will simultaneously
be increased by the degree of contamination to reproduce the
original sensitivity to smoke.
There may be an automatic order to exchange the detector if the
60% threshold is reached.
(approx. 30% has been compensated)
At 80% of the alarm threshold the detector is extremely
contaminated; compensation is no longer possible.
The risk of alarms has increased considerably.
The detector deactivates its measuring system.
The LED flashes yellow.