Product Information Optical Smoke Detector NOM/NOM K 100 LSN
Seite 13 von 30
BDL
−
F.01U.002.709
A5.en / 29.12.2004
ST
−
FIR/ PRM1 / deh
6.3. Monitoring Stages
Alarm signaling takes place at different thresholds for smoke and contamination.
For smoke
The evaluation is made during smoke measurement using the scattered light
measured and the resulting current.
If specific thresholds, defined in the detector, are exceeded, the detector issues a
corresponding message.
−
at 50%: pre
−
alarm message to the control panel
−
at 100%: alarm message to the control panel
A fault message is triggered if the smoke volume falls below the 0% threshold by
approx. 20%.
0%
Time
Quiescent state value
Alarm current
100%
Pre
−
alarm
Fault
50%
Detector pre
−
alarm
Can be called up for maintenance purposes
Quiescent state potential with new detector
approx. 1/5 below quiescent state potential
Detector not sensitive enough
Alarm
Alarm signaling by detector