6 720 874 421 (2017/04) ZA
Mini VRF Heat Pump Outdoor Unit
4 | OUTDOOR UNIT INSTALLATION
H
A
Fig. 3-2
B
C
D
E
F
Fig. 3-3
MODEL (kW)
A
B
C
D
E
F
G
H
Fig.
8/10.5
990 624 380 339 396 366 1073 966
Fig. 3-1
Fig. 3-3
12/14/16/18
1280 600 366 320 400 360
–
1327
Fig. 3-2
Fig. 3-3
•
Single unit installation
>300
>600
>
300
>
2000
(Wall or obstacle)
Maintain
cha
nnel
Air outlet
Air inlet
Air inlet
Fig. 3-4
•
Parallel connection of two or more units.
>600
>2000
>300
Fig. 3-5
•
Parallel connection for units facing each other.
>2000
>500
>3000
>3000
>300
Fig. 3-6
3.3 Handling and installation
•
Caution must be taken when handling the outdoor unit, the
weight is not in the centre of the unit. The unit is heavier on the
front right side. For lifting advice consult HSE and use specified
lifting equipment.
•
Do not touch the fan blades. The fan blades are sharp and could
cause an injury.
•
When handling the unit, ensure you do not lean the unit more than
45 degrees as this will cause internal damage to the compressor.
•
Fasten the feet of this unit with bolts firmly to prevent it from
toppling over.
(Refer to Fig. 3-7)
>
6
0
c
m
Fix with bolt
Fig. 3-7
NOTE
All the pictures in this manual are for illustration purposes only. The
illustrations may be slightly different from the air conditioning unit you have
purchased (dependent on model).
3.4 Condensate Outlet
There are four condense water outlets on the body of the unit shown on
the figure below.
Reserve water outlet
Reserve water outlet
Water Outlet
Outlet for power and connecting pipes
Remove knockout
if required
(With rubber stopper)
Fig. 3-8
CAUTION
When installing the outdoor unit, consider the drainage points.