5.
Follow the same steps to log on the next radio device.
All the radio devices are now logged on and form a radio cell.
6.
Wait until LED
(H4) on the radio gateway goes out.
7.
Check that the number of logged-on radio devices in the radio cell is complete.
Check that the internal alarm indicators of all the radio devices are off.
1.
To switch the radio cell to normal operation, press and hold button
(S1) for at least
2
seconds.
2.
Wait until the LED
(H2) goes out.
The radio cell is in normal operation.
3.
If the radio gateway is not yet connected to the fire panel disconnect the battery of the
radio gateway.
P
All the radio devices have now been read in at the fire control panel.
4
Use the FXS2061 to back up the network file. The procedure for backing up the network
file is described in more detail in the User Guide FXS2061.
Commissioning the radio gateway
The radio gateway is installed.
The radio gateway is connected to the fire panel.
A computer with FSP-5000-RPS installation is at hand and connected to the fire panel.
The user is familiar with the corresponding fire panel documentation.
1.
Start RPS on your computer.
2.
Open a configuration file and configure the radio gateway:
- Automatically by auto-detection from the node or LSN module context menu
- Manually by adding it to the LSN module at its correct physical position
1.
Download the configuration to the fire panel.
2.
Wait for the fire panel to restart.
P
The radio gateway is commissioned
Commissioning the radio cell
The radio gateway is commissioned.
The radio gateway battery is connected.
The radio cell is set up.
A computer with the latest FSP-5000-RPS programming software installation is at hand and
connected to the fire panel.
The user is familiar with the corresponding fire panel documentation.
1.
Start FSP-5000-RPS on your computer.
2.
Open a configuration file and configure the radio cell:
Automatically: by auto-detect radio devices from the radio gateway context menu
Manually: by adding the radio devices to the radio gateway and entering their correct ID
numbers
3.
Download the configuration to the fire panel.
4.
Wait for the fire panel to restart.
P
The radio cell is commissioned
Refer to
–
Basic rules for commissioning, page 30
–