28
en | Mounting /Installation
Radio gateway
2019.10 | 2.0 | F.01U.373.488
Operation Manual
Bosch Sicherheitssysteme GmbH
U+, 0V
Auxiliary power supply
BAT
Battery connector
Refer to
–
Master gauge for recesses, page 50
–
Connecting the radio gateway, page 28
5.1
Connecting the radio gateway
Specialist electrical engineering knowledge is required for
installation.
Only an expert is permitted to carry out installation work.
Incorrect installation can take safety devices out of operation
unbeknown to a layperson.
NOTICE
Failure of the electrical connection
Damage to the screw terminals or contact problems may lead to
faults in the electrical connection. If the conductor cross-sections
you want to connect to the radio gateway are larger than 1.5
mm²,
the screw terminals may become damaged or contact problems may
arise.
Once all the radio devices of a radio cell have been logged on to the radio gateway
(B) in
battery mode (A), the radio gateway can be connected to the LSN line and auxiliary power
supply (C).
The radio cell can be setup in the battery mode as shown in following graphic or can be set up
by using the auxiliary power (LSN AUX) or BCM (24V).