22
en | Planning
Radio gateway
2019.10 | 2.0 | F.01U.373.488
Operation Manual
Bosch Sicherheitssysteme GmbH
Figure
4.6: Floorplan
For the radio fire detection system to work as well as possible, radio
devices must be placed in central areas such as corridors. Include
1-2 spare radio devices in the plan for any modification work that
may need to be carried out after commissioning.
Positioning the radio gateway
The radio gateway should be installed in a central location within the radio cell. Make sure
that there are no large metal objects in the immediate vicinity of the radio gateway. These may
have a negative effect on radio links.
Checking the range
Check the radio device ranges as indicated in the planning specifications.
1.
Mark all the radio devices that are directly within the radio gateway range.
2.
Using a different color, mark all the radio devices that are within the ranges of those radio
devices you have already marked.
3.
Using a different color again, mark all the radio devices that are within the ranges of
those radio devices you have already marked.
4.
If a radio link passes through two walls (exclusion zone), an additional radio device must
be included in the range plans.