30
en | Commissioning
Radio gateway
2019.10 | 2.0 | F.01U.373.488
Operation Manual
Bosch Sicherheitssysteme GmbH
6
Commissioning
There are two operating conditions for radio cells.
Normal operation
The radio cell is active and ready for use. Information is transmitted to the LSN line via the
radio gateway.
Maintenance mode
The radio cell is active but not ready for use. Information is not transmitted to the LSN line via
the radio gateway. The radio cell can be modified.
6.1
Basic rules for commissioning
Requirements for reliable radio device connections:
–
Radio cells whose areas of coverage overlap must not be in maintenance mode at the
same time. This means that you should only ever switch one radio cell at a time to
maintenance mode.
Sequence for commissioning radio devices
Working outwards from the radio gateway, commission the individual radio devices one after
the other. The graphic below serves as an example of the correct sequence for commissioning
radio devices.
Figure
6.1: Example: Correct sequence for commissioning radio devices
Radio gateway
Radio device