en | Operation
Conventional Fire Panel
F.01U.172.982 | 5.0 | 2012.04
Operation Guide
Bosch Sicherheitssysteme GmbH
EVAC button functions
The EVAC button has various functions, depending on the
status of the fire panel:
–
Panel in normal state
You can trigger a test alarm using the EVAC button.
–
Panel in alarm state
If you have silenced the notification appliances, you can
reactivate them using the EVAC button.
–
Panel in alarm verification, dual-zone dependency, or dual-
detector dependency state
The delay for the alarm notification appliances is ended.
The notification appliances are triggered immediately.
Silencing notification appliances
4.2.2
Test/Disablements Menu
The following options are available in the test menu:
–
1-Test MMI
–
2-Test Zones
Press the "Evacuation" key.
–
Press the ACK key.
The fire panel activates all notification appliances and
relays as programmed.
–
Press the "Reset" key.
No evacuation is triggered.
EVAC
ACK
RESET
NOTICE!
Only silence an alarm once you have made sure that there is not
actually a fire.
You can reactivate silenced alarm devices using the EVAC
button.
Press the "Silence notification appliance" key.
The fire panel deactivates all notification appliances and
relays as programmed. A new alarm reactivates the
notification appliances and relays, if programmed.