Conventional Fire Panel
| en
29
Bosch Sicherheitssysteme GmbH
Operation Guide
F.01U.172.982 | 5.0 | 2012.04
A
Appendix
A.1
Event Memory
Message
Meaning
Drill/Evacuate
A manual alarm has been triggered on the panel.
Zone # Alarm
Zone # has triggered an alarm.
Zone # PreAlarm
Zone # has triggered a pre-alarm.
Zone # Open
Zone # is interrupted.
Zone # Short
Zone # has a short-circuit.
Zone # Normal
Zone # is in the normal state. (Fault or alarm
eliminated)
Zone # Disabled
Zone # is disabled.
Zone # Enabled
Zone # was enabled.
Input # Open
Input # interrupted.
Input # Short
Input # short-circuit.
Input # Normal
Input # normal.
Aux Power Short
Short-circuit in the AUX power supply
Aux Power Normal
Fault in the AUX power supply rectified.
NAC # Open
Notification appliance #, line interrupted
NAC # Short
Notification appliance #, short-circuit on line.
NAC # Normal
Notification appliance # normal. (Fault was
eliminated)
NAC Enabled
Notification appliances re-enabled.
NAC Disabled
Notification appliances disabled.
Relays Enabled
Relays re-enabled.
Relays Disabled
Relays disabled.
Battery Fault
Fault in the battery power supply.
Battery Restore
Battery power supply was restored.
Mains Fault
Fault in the 230 V power supply.
Mains Restore
230 V power supply was restored.
Ext PS Fault
Fault in external power supply unit.
Ext PS Normal
Fault in external power supply unit resolved.
Ext BATT Fault
Fault in external battery.
Ext BATT Normal
Fault in external battery resolved.
Sys Load Fault
Current consumption of panel and all connected
peripherals is above 3.5 A.
Sys Load Normal
Current consumption is back in permitted range.
System Fault
System fault
Panel boot-up
Panel has been restarted.
Reset Panel
Panel has been reset.