LSN 1500 A LSN improved Module 1500 mA
This module can be used to connect an LSN loop with
–
up to 254 LSN improved elements with a max. line current of 1500 mA and a cable length
of up to 3000 m (depending on configuration and cable type)
–
up to 127 classic LSN elements with a max. line current of 300 mA and a cable length of
up to 3000 m (depending on configuration and cable type).
!
Caution!
The module may only be connected to a PRD 0004 A Panel Rail Long, where it requires two
slots (see
Installation in Panel Rail, page 114).
The module must be connected to the first two slots on the left of the panel rail.
Notice!
To ensure that the fire detection system is operated in compliance with EN 54‑13, each LSN
stub and T-tap must be terminated with EOL modules.
Figure 4.64:
LSN 1500 A LSN improved Module 1500 mA
Labeling
Connection
LSN loop
LSN stub
AUX1 + | AUX1 -
Auxiliary power supply
Auxiliary power supply for stub 1
LSN a1- | LSN b1+
LSN a1- / LSN b1+ outgoing
Stub 1 LSN a1-/stub 1 LSN b1+
AUX2 + | AUX2 -
Auxiliary power supply*
Auxiliary power supply for stub 2
LSN a2- | LSN b2+
LSN a2- / LSN b2+ incoming
Stub 2 LSN a2-/stub 2 LSN b2+
* The auxiliary voltage may only be fed back to AUX2 when isolators (ERT technology) are
used in the loop (suitable components include YBO-R/SCI isolators).