Modular fire panel
Technical Data | en
153
Bosch Sicherheitssysteme GmbH
System Information
07.2020 | 12.0 | F.01U.028.089
Space required (H x W x D)
approx. 127 x 96 x 60 mm
Weight
approx. 180 g
7.5.9
LSN 0300 A LSN improved Module 300 mA
Operating and display elements
2 LEDs (1 x red, alarm/ 1 x yellow, fault)
1 button (LED test)
Input voltage
20 V DC to 30 V DC
Output voltage
–
LSN standby voltage
30 ± 1.0 V DC
–
LSN transmission voltage
30 ± 1.0 V DC + 1.6 ± 0.15 V DC (voltage range)
–
Auxiliary supply AUX
28 ± 1.0 V DC
Maximum current consumption
1750 mA at 24 V DC
Nominal current consumption
–
Module
39 mA at 24 V DC
–
LSN
1.7 x current consumption of the LSN elements
–
AUX
1.2 x auxiliary supply AUX
Cable length
max. 1600 m, depending on configuration and cable
type
Number of LSN elements
max. 127 LSN classic elements
max. 254 LSN improved elements
LSN line current
max. 300 mA, depending on configuration and cable
type
Auxiliary supply AUX
(28 V DC)
max. 500 mA for an LSN loop (ERT technology) or 2 x
max. 500 mA with 2 stubs
Space required (H x W x D)
approx. 127 x 96 x 60 mm
Weight
approx. 225 g
7.5.10
LSN 1500 A LSN improved Module 1500 mA
Operating and display elements
2 LEDs (1 x red, alarm/1 x yellow, fault)
1 button (LED test)
Input voltage
20 V DC to 30 V DC
Output voltage
–
LSN
30 ± 0.85 V DC
–
Auxiliary supply AUX
28 ± 1.0 V DC
Maximum current consumption
4010 mA at 24 V DC
Nominal current consumption
–
Module
260 mA at 24 V DC
Summary of Contents for FPA-1200
Page 1: ...Modular fire panel FPA 5000 FPA 1200 en System Information ...
Page 2: ......
Page 173: ......