154
en | Technical Data
Modular fire panel
07.2020 | 12.0 | F.01U.028.089
System Information
Bosch Sicherheitssysteme GmbH
–
LSN
1.7 x current consumption of the LSN elements
–
AUX
1.2 x auxiliary supply AUX
Cable length
max. 3000 m, depending on configuration and cable type
Number of LSN elements
Max. 127 LSN classic elements
Max. 254 LSN improved elements
LSN line current
–
Standby
max. 750 mA, depending on configuration and cable type
–
Alarm
max. 1500 mA, depending on configuration and cable
type
max. 300 mA when connecting LSN classic elements
Auxiliary supply AUX
(28 V DC)
max. 500 mA for an LSN loop (ERT technology) or 2 x
max. 500 mA with 2 stubs
Space required (H x W x D)
approx. 127 x 190 x 60 mm
Weight
approx. 440 g
7.5.11
NZM 0002 A Notification Appliance Zone Module
Operating and display elements
4 LEDs (2 x red, alarm/2 x yellow, fault)
2 buttons (LED test)
Input voltage
20 V DC to 30 V DC
Maximum current consumption
–
Standby mode (both zones)
40 mA
–
In case of alarms (both zones)
65 mA + 500 mA per notification appliance
Maximum output voltage
29.5 V DC
Maximum output current
–
For supply via panel rail
500 mA per notification appliance (in case of
alarm)
–
For external power supply
3 A per notification appliance (in case of
alarm)
Space required (H x W x D)
approx. 127 x 96 x 60 mm
Weight
Approx. 135 g
7.5.12
RMH 0002 A Relay Module for mains voltage
Operating and display elements
4 LEDs (2 x red, alarm/2 x yellow, fault)
2 buttons (each on/off)
Fuses
F1 = T 6.3 A, F2 = T 6.3 A
Input voltage
20 V DC to 30 V DC
Feedback current
max. 8.5 mA per feedback output