FMR-7033 

|

 

Installation Instructions | 1.0 

Introduction 

 

Bosch Security Systems, Inc. | 9/08 | F01U010583-01 

3

1.0 Introduction 

These instructions cover the installation of the Bosch 
Security Systems, Inc. (Bosch) FMR-7033 Addressable 
Fire System Controller in a fire system supervised by a 
Bosch FPD-7024 Fire Alarm Control Panel (FACP). 

 

Follow these instructions to avoid personal 
injury and/or damage to equipment. 

 

 

 

 

Install, test, and maintain these devices 
according to these instructions, NFPA 72, 
Local Codes, and the Authority Having 
Jurisdiction (AHJ). Failure to follow these 
instructions might result in failure of the 
device to initiate a proper response. Bosch 
is not responsible for improperly installed, 
tested or maintained devices. 

2.0 Description 

The FMR-7033 Addressable Fire System Controller is 
a four-wire alphanumeric LCD keypad that combines 
fire system annunciator and controller functions. It 
operates identically to the built-in user interface on the 
FACP. Up to four FMR-7033 controllers might be 
connected to an FPD-7024. 

The FMR-7033 can be surface mounted, mounted to a 
single or double gang box or to a four-inch square box. 

3.0 Device 

Mounting 

The FMR-7033 should be mounted no higher than 
shoulder height of the shortest person using the system. 

Remove the keypad’s cover by inserting a small flat-
head screwdriver in each slot at the bottom of the base. 
Press up and pull the cover off (

Figure 1

). 

 

Figure 1: 

Removing the FMR-7033 Cover 

(Bottom front view of FMR-7033)

1

2

1 -  Keypad Keys 

2  

Insert small flat screwdriver in each slot to 
remove FMR-7033 cover 

3.1 

Mounting the FMR-7033 to a Surface 

1. 

Use the base as a template and mark the location 
of the mounting holes (use any holes). 

2. 

Provide an opening in the mounting surface for 
the wiring. 

3. 

Partially install the mounting screws. 

 

Do not tighten the mounting screws. 

3.2 

Mounting the FMR-7033 to an 
Electrical Box 

Refer to 

Figure 2

 on page 5 to select mounting holes. 

Do not tighten the mounting screws. 

 

Summary of Contents for FMR-7033

Page 1: ...FMR 7033 EN Installation Instructions Addressable Fire System Controller ...

Page 2: ... Label and Slide 5 7 0 Setting the FMR 7033 s Address 5 8 0 Programming the FMR 7033 5 9 0 Troubleshooting the FMR 7033 5 10 0 Specifications 6 11 0 Operating the FMR 7033 7 Figures Figure 1 Removing the FMR 7033 Cover 3 Figure 2 Location of the FMR 7033 Base Mounting Holes 4 Figure 3 Wiring the FMR 7033 s Terminal Strip 4 Figure 4 Installing the Instruction Label and Slide 5 Figure 5 FMR 7033 Key...

Page 3: ...er functions It operates identically to the built in user interface on the FACP Up to four FMR 7033 controllers might be connected to an FPD 7024 The FMR 7033 can be surface mounted mounted to a single or double gang box or to a four inch square box 3 0 Device Mounting The FMR 7033 should be mounted no higher than shoulder height of the shortest person using the system Remove the keypad s cover by...

Page 4: ...1 2 mm Wire Type Non shielded 4 wire Maximum number of keypad allowed per system 4 Distance allowed between FACP and Keypad 2000 ft 610 m Maximum distance of keypad wiring and bus 4000 ft 1219 m To wire the FMR 7033 Fire System Controller 1 Route the wiring from the FACP to the keypads Refer to the FACP s installation guide for details 2 Bring the base wiring through the wire entrance in the keypa...

Page 5: ... must not conflict with the addresses of other keypads or other option bus devices Each keypad address can support only one device All keypads must also be programmed at the FACP Select the keypad address 1 15 by placing the shorting jumpers over the address pins as shown in Figure 5 Figure 5 FMR 7033 Keypad Addresses 1 2 4 8 1 2 4 8 1 2 4 8 1 2 4 8 1 2 4 8 Address 1 Address 4 Address 7 Address 10...

Page 6: ...FACP does not respond to keypad input The keypad s address was not set Three beep error tone at all keypads Invalid key input 10 0 Specifications Table 3 FMR 7033 Specifications Nominal Supply Voltage 12 VDC from Option Bus Standby Current 100 mA 75 mA for battery calculation Alarm Current 100 mA 75 mA for battery calculation Environment Use Indoor Dry Operating Temperature 32 F to 120 F 0 C to 49...

Page 7: ...ets the bell or sirens for an alarm or trouble condition only if the system is so configured 1 The two line character display can show all messages normally displayed on an FPD 7024 or an FMR 7036 keypad 2 The red Alarm LED lights whenever the system registers an alarm and was not reset 3 The yellow Silenced LED lights when the user manually silences an alarm or trouble condition It turns off when...

Page 8: ... 2008 Bosch Security Systems Inc F01U010583 01 Bosch Security Systems Inc 130 Perinton Parkway Fairport NY 14450 9199 800 289 0096 www boschsecurity com ...

Reviews: