background image

FMR-7033 

|

 

Installation Instructions | 11.0 

Operating the FMR-7033 

 

Bosch Security Systems, Inc. | 9/08 | F01U010583-01 

7

11.

 

Use the [Test] key to select one of seven 
special test modes (refer to 

FPD-7024 O&I 

Guide

; P/N F01U008458). 

11.0  Operating the FMR-7033 

 

12.

 

Use the [Disable] key to disable or re-enable 
inputs NACs or relays (outputs), and the 
dialer.  

 

Figure 6: 

Keypad Features 

Alarm

Si lenced

Su per viso ry

Tr oub le

1

2

3

4

5

6

7

8

9

0

Pro gr am

*

#

Ente r

Silence

Dr ill

Test

Disable

Re set

ACK

Ba ck

History

TE ST WEEK LY

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

 

13.

 

Use the [Drill] key to activate the NACs 
manually. It creates a history log entry and can 
be optionally reported to the central station. 

14.

 

The [Reset] key (programmable from 1 to 16 
sec) briefly turns off power to the detectors to 
reset them and clears any off-normal 
conditions. 

15.

 

Use the [Acknowledge] key to silence local 
keypad sounders and to view off-normal 
conditions. 

16.

 

The [Silence] key quiets the bell or sirens for 
an alarm or trouble condition only if the system 
is so configured. 

 

 

1.

 

The two-line character display can show all 
messages normally displayed on an FPD-7024 
or an FMR-7036 keypad. 

2.

 

The red Alarm LED lights whenever the system 
registers an alarm and was not reset. 

3.

 

The yellow Silenced LED lights when the user 
manually silences an alarm or trouble 
condition. It turns off when the condition that 
was silenced is corrected. 

4.

 

The yellow Supervisory LED lights whenever 
the system registers a supervisory condition. 

5.

 

The yellow Trouble LED lights whenever the 
system detects a problem with wiring or 
internal circuitry. The Trouble LED flashes 
while programming mode is active and 
whenever inputs are not active, such as during 
smoke power reset or alarm verification. 

6.

 

Scroll keys are used to move through the off-
normal events indicated on the display. 

7.

 

During the programming, use the [Back] key to 
exit from menus or exit from the programming 
mode entirely. 

8.

 

Use the [Programming] key to select the 
programming mode. 

9.

 

Use the [History] key to view system events. 

10.

 

Use the [Enter] key to accept data when in the 
programming mode. 

 

Summary of Contents for FMR-7033

Page 1: ...FMR 7033 EN Installation Instructions Addressable Fire System Controller ...

Page 2: ... Label and Slide 5 7 0 Setting the FMR 7033 s Address 5 8 0 Programming the FMR 7033 5 9 0 Troubleshooting the FMR 7033 5 10 0 Specifications 6 11 0 Operating the FMR 7033 7 Figures Figure 1 Removing the FMR 7033 Cover 3 Figure 2 Location of the FMR 7033 Base Mounting Holes 4 Figure 3 Wiring the FMR 7033 s Terminal Strip 4 Figure 4 Installing the Instruction Label and Slide 5 Figure 5 FMR 7033 Key...

Page 3: ...er functions It operates identically to the built in user interface on the FACP Up to four FMR 7033 controllers might be connected to an FPD 7024 The FMR 7033 can be surface mounted mounted to a single or double gang box or to a four inch square box 3 0 Device Mounting The FMR 7033 should be mounted no higher than shoulder height of the shortest person using the system Remove the keypad s cover by...

Page 4: ...1 2 mm Wire Type Non shielded 4 wire Maximum number of keypad allowed per system 4 Distance allowed between FACP and Keypad 2000 ft 610 m Maximum distance of keypad wiring and bus 4000 ft 1219 m To wire the FMR 7033 Fire System Controller 1 Route the wiring from the FACP to the keypads Refer to the FACP s installation guide for details 2 Bring the base wiring through the wire entrance in the keypa...

Page 5: ... must not conflict with the addresses of other keypads or other option bus devices Each keypad address can support only one device All keypads must also be programmed at the FACP Select the keypad address 1 15 by placing the shorting jumpers over the address pins as shown in Figure 5 Figure 5 FMR 7033 Keypad Addresses 1 2 4 8 1 2 4 8 1 2 4 8 1 2 4 8 1 2 4 8 Address 1 Address 4 Address 7 Address 10...

Page 6: ...FACP does not respond to keypad input The keypad s address was not set Three beep error tone at all keypads Invalid key input 10 0 Specifications Table 3 FMR 7033 Specifications Nominal Supply Voltage 12 VDC from Option Bus Standby Current 100 mA 75 mA for battery calculation Alarm Current 100 mA 75 mA for battery calculation Environment Use Indoor Dry Operating Temperature 32 F to 120 F 0 C to 49...

Page 7: ...ets the bell or sirens for an alarm or trouble condition only if the system is so configured 1 The two line character display can show all messages normally displayed on an FPD 7024 or an FMR 7036 keypad 2 The red Alarm LED lights whenever the system registers an alarm and was not reset 3 The yellow Silenced LED lights when the user manually silences an alarm or trouble condition It turns off when...

Page 8: ... 2008 Bosch Security Systems Inc F01U010583 01 Bosch Security Systems Inc 130 Perinton Parkway Fairport NY 14450 9199 800 289 0096 www boschsecurity com ...

Reviews: