FMR-7033
|
Installation Instructions | Specifications
6
Bosch Security Systems, Inc. | 9/08 | F01U010583-01
Table 2:
FMR-7033 Troubleshooting Tips
FMR-7033 Keypad
Notification
Possible Causes
Continuous keypad sounder
plus “System Fault” display
-
The yellow and green
ground wires are
disconnected.
-
The keypad is not
programmed properly at
the FACP.
-
The FACP
malfunctioned. Replace
the FACP.
FACP does not respond to
keypad input
-
The keypad’s address
was not set.
Three-beep error tone at all
keypads
-
Invalid key input.
10.0
Specifications
Table 3:
FMR-7033 Specifications
Nominal Supply Voltage
12 VDC from Option Bus
Standby Current
100 mA (75 mA for battery
calculation)
Alarm Current
100 mA (75 mA for battery
calculation)
Environment
Use Indoor/Dry
Operating Temperature
+32°F to 120°F (0°C to
+49°C)
Relative Humidity
93%
Width
6.25 in (15.9 cm)
Height
4.6 in (11.7 cm)
Depth
1.3 in (2.9 cm)
Listings and Approvals
UL864, FM
Wiring
Supervised Communication
Circuit Class B, Style 4