FMR-7033 

|

 

Installation Instructions | 6.0 

Installing the FMR-7033 Instruction Label and Slide 

 

Bosch Security Systems, Inc. | 9/08 | F01U010583-01 

5

For battery standby calculations, assume that the  
FMR-7033 draws 75 mA from the 24 VDC battery. 
The FPD-7024 FACP uses a switching power supply to 
convert 24 VDC battery power to 12 VDC option bus 
power. This conversion reduces the current drawn 
from the battery. 

 

6.0  Installing the FMR-7033 

Instruction Label and Slide 

An instruction label is provided for placement on the 
pullout slide. The slide can be installed to pull from the 
left or right (slide it into rear of base). 

 

 

Use care when installing the label. Place it 
as close to the pull-tab as possible. 

 

Figure 4: 

Installing the Instruction Label and 
Slide 

Slide in either side

Back of FMR-7033 Keypad

Label

Label

Label

(writing on other side)

7.0  Setting the FMR-7033’s 

Address 

 

 

Each keypad must have its own address 
set with its address pins. This address 
must not conflict with the addresses of 
other keypads or other option bus devices. 
Each keypad address can support only one 
device. All keypads must also be 
programmed at the FACP. 

Select the keypad address (1-15) by placing the 
shorting jumpers over the address pins as shown in 

Figure 5.

 

Figure 5: 

FMR-7033 Keypad Addresses 

1

2

4

8

1

2

4

8

1

2

4

8

1

2

4

8

1

2

4

8

Address 1

Address 4

Address 7

Address 10

Address 13

1

2

4

8

1

2

4

8

1

2

4

8

1

2

4

8

1

2

4

8

Address 2

Address 5

Address 8

Address 11

Address 14

1

2

4

8

1

2

4

8

1

2

4

8

1

2

4

8

1

2

4

8

Address 3

Address 6

Address 9

Address 12

Address 15

8.0  Programming the  

FMR-7033 

The control panel does not recognize the keypad until 
the option bus is updated. 

To update the option bus from the local keypad: 

1. 

Enter programming mode using the correct 
programming code. 

2. 

Select menu item 3 – System. 

3. 

Select menu item 4 – Option Bus 

4. 

Select menu item 1 – Update Bus 

5. 

Press */back to exit from programming mode. 

 

Ensure that the number of devices found 
on the bus agrees with the number 
installed. 

 

9.0  Troubleshooting the  

FMR-7033 

Refer to 

Table 2

 on page 6 when troubleshooting 

problems with the FMR-7033. 

Summary of Contents for FMR-7033

Page 1: ...FMR 7033 EN Installation Instructions Addressable Fire System Controller ...

Page 2: ... Label and Slide 5 7 0 Setting the FMR 7033 s Address 5 8 0 Programming the FMR 7033 5 9 0 Troubleshooting the FMR 7033 5 10 0 Specifications 6 11 0 Operating the FMR 7033 7 Figures Figure 1 Removing the FMR 7033 Cover 3 Figure 2 Location of the FMR 7033 Base Mounting Holes 4 Figure 3 Wiring the FMR 7033 s Terminal Strip 4 Figure 4 Installing the Instruction Label and Slide 5 Figure 5 FMR 7033 Key...

Page 3: ...er functions It operates identically to the built in user interface on the FACP Up to four FMR 7033 controllers might be connected to an FPD 7024 The FMR 7033 can be surface mounted mounted to a single or double gang box or to a four inch square box 3 0 Device Mounting The FMR 7033 should be mounted no higher than shoulder height of the shortest person using the system Remove the keypad s cover by...

Page 4: ...1 2 mm Wire Type Non shielded 4 wire Maximum number of keypad allowed per system 4 Distance allowed between FACP and Keypad 2000 ft 610 m Maximum distance of keypad wiring and bus 4000 ft 1219 m To wire the FMR 7033 Fire System Controller 1 Route the wiring from the FACP to the keypads Refer to the FACP s installation guide for details 2 Bring the base wiring through the wire entrance in the keypa...

Page 5: ... must not conflict with the addresses of other keypads or other option bus devices Each keypad address can support only one device All keypads must also be programmed at the FACP Select the keypad address 1 15 by placing the shorting jumpers over the address pins as shown in Figure 5 Figure 5 FMR 7033 Keypad Addresses 1 2 4 8 1 2 4 8 1 2 4 8 1 2 4 8 1 2 4 8 Address 1 Address 4 Address 7 Address 10...

Page 6: ...FACP does not respond to keypad input The keypad s address was not set Three beep error tone at all keypads Invalid key input 10 0 Specifications Table 3 FMR 7033 Specifications Nominal Supply Voltage 12 VDC from Option Bus Standby Current 100 mA 75 mA for battery calculation Alarm Current 100 mA 75 mA for battery calculation Environment Use Indoor Dry Operating Temperature 32 F to 120 F 0 C to 49...

Page 7: ...ets the bell or sirens for an alarm or trouble condition only if the system is so configured 1 The two line character display can show all messages normally displayed on an FPD 7024 or an FMR 7036 keypad 2 The red Alarm LED lights whenever the system registers an alarm and was not reset 3 The yellow Silenced LED lights when the user manually silences an alarm or trouble condition It turns off when...

Page 8: ... 2008 Bosch Security Systems Inc F01U010583 01 Bosch Security Systems Inc 130 Perinton Parkway Fairport NY 14450 9199 800 289 0096 www boschsecurity com ...

Reviews: