background image

DS939 Ceiling Mount

PIR Intrusion Detector

1.0

Specifications

Dimensions

3.5 in. x 7 in. (8.9 cm x 17.8 cm)

(HxDia):

Coverage:

360° by 70 ft. (21 m) diameter coverage when
mounted on 12 to 25 ft. (3.7 to 7.6 m) high ceilings. A
coverage area of 40 ft. (12 m) is available when
mounted at 8 ft. (2.4 m) and a coverage of 50 ft.
(15 m) is available when mounted at 10 ft. (3 m). The
pattern consists of 69 zones grouped into 21 barriers.
Each barrier is 35 ft. (10.7 m) long and 5 ft. (1.5 m)
wide at 35 ft. (10.7 m). The barriers are divided into 3
groups of 7 barriers, each of which has a vertical
adjustment for custom coverage.

Input

9.0 to 15.0 VDC; 22 mA standby, 39 mA in alarm with

Power:

LEDs enabled. Use only a Listed Limited Power
Source.

Standby

There is no internal standby battery. 22 mAh is

Power:

required for each hour of standby time needed. 

For UL

Listed Requirements, four hours of standby current
(88 mAh) is required. Standby power must be
provided by a Listed Limited Power Source.

Sensitivity:

Low/High settings.

Alarm

Silent-operating Form “C” relay. Contacts rated 125

Relay:

mA, 28 VDC, 3 watts maximum for DC resistive loads.
The contacts transfer on alarm for a period of 4
seconds. Some countries require the relay to be
connected to a SELV (Safety Extra-Low Voltage)
circuit only. Do not use with capacitive or inductive
loads.

Tamper:

Normally Closed (with cover in place) tamper switch.
A wall (base) tamper is included. Contacts rated at 28
VDC, 125 mA, 3 watts maximum. Some countries
require the switch to be connected to a SELV (Safety
Extra-Low Voltage) circuit only. Connect tamper circuit
to a 24-hour protection circuit.

Temperature

The storage and operating range is -40° to +120°F

Range:

(-40° to +49°C). 

For UL Listed Requirements, the

range is +32° to +120°F (0° to +49°C).

US Patent

This detector is protected by one or more of the

Numbers:

following: #4,764,755. Other patents pending.

Compliance:

This device complies with Part 15 of the FCC Rules
and with RSS-210 of Industry and Science Canada.
Operation is subject to the following two conditions:
(1) this device may not cause harmful interference,
and
(2) this device must accept any interference
received, including interference that may cause
undesirable operation.
Changes or modifications not expressly approved by
Bosch Security Systems can void the user’s authority
to operate the equipment.

2.0

Installation Considerations

Never install the detector in an environment that causes an alarm
condition. Good installations start with the LED OFF when there is no
target motion. It should never be left to operate with the LED in a
constant or intermittent alarm (red) condition.

Avoid installations where rotating machines (e.g. ceiling fans) are
normally in operation within the coverage pattern. Point the unit away
from glass exposed to the outdoors and objects that may change
temperature rapidly.

Note:

The PIR detector will react to objects rapidly changing temperature
within its field-of-view.

For optimum detection, select a location likely to intercept an intruder
moving 

across the coverage pattern.

3.0

Mounting

Recommended mounting height range is 12 to 25 feet (3.7 to 7.6 m). A
coverage area of 40-70 ft. (12.2-21.3 m) is available when mounted
between 8-12 ft. (2.4-3.7 m).

The surface should be solid and vibration-free. (i.e. drop tiles should be
secured if the area above the tiles is used as an air return for HVAC
systems).

To open the detector, locate the arrow on the cover of the detector 

.

Turn a screwdriver in the recess between the cover and the base 

.

One side of the cover will remain attached to the base of the detector.

Summary of Contents for DS939

Page 1: ... C For UL Listed Requirements the range is 32 to 120 F 0 to 49 C US Patent This detector is protected by one or more of the Numbers following 4 764 755 Other patents pending Compliance This device complies with Part 15 of the FCC Rules and with RSS 210 of Industry and Science Canada Operation is subject to the following two conditions 1 this device may not cause harmful interference and 2 this dev...

Page 2: ...ly NO C NC T T M ALARM TAMPER POWER Terminals 1 2 Power limits are 9 to 15 VDC Use no smaller than 22 AWG 0 8 mm wire pair between the unit and the power source Terminals 3 NO 4 C 5 NC Alarm relay contacts rated 125 mA 28 VDC maximum for DC resistive loads Use terminals 4 5 for Normally Closed circuits Do not use with capacitive or inductive loads Terminals 6 T 7 T Normally Closed tamper contacts ...

Page 3: ...e Walk Test if OFF ON for more than 5 seconds but less than 20 seconds OFF Turn OFF Remote Walk Test if ON ON for more than 1 second but Less than 20 seconds OFF 8 2 Anti Vandal Screw After the cover has been closed the entire assembly can be secured together using the supplied anti vandal screw 8 3 Maintenance At least once a year the range and coverage should be verified To ensure continual dail...

Page 4: ...ing height of the detector The range shown is the distance from the detector to the outside edge of the coverage pattern Mounting Height Feet Meters Maximum Range Feet Meters 8 2 4 10 3 12 3 7 14 4 3 15 4 6 16 4 9 18 5 5 20 6 1 22 6 7 24 7 3 25 7 6 10 3 C A 15 4 6 G D A A 20 6 1 I G D B A A 25 7 6 I F E D C A A 30 9 1 H F E E C B A 35 10 7 I G G F E C B A A In installations where a targeted covera...

Reviews: