11.5
SDI Address 80
SDI Address 80, available on the D9412G/D7412G
panels, allows for bi-directional SDI to RS-232
information. This address is used with home or building
automation software. A D9133 Serial Interface Module is
required for this application.
11.5.1
D9133 Serial Interface Module
The D9133 Serial Interface Module is a 4-wire powered
SDI device providing connection for RS-232 devices to
the D9412G/D7412G Control Panels. D9133 uses a
specific communication protocol that is provided upon
request. Contact Bosch Security Systems Technical
Support Monday through Friday from 5 AM to 5 PM
EST at 888-886-6189.
The D9133 can be installed up to 305 m (1000 ft.) from
the panel using 1.2 mm (18 AWG) wire. D9133 is not UL
Listed.
11.5.2
Address Settings
There are no jumper settings required for the D9133
(SDI Address 80) for home or building automation
purposes (see Figure 28). Remove jumper shunts for this
setting.
11.0 SDI Devices
11.5.3
Supervision
Supervision of the D9133 is available through
programming that includes proper operation between
the D9133 and the control panel.
If supervised and the D9133 does not respond to panel
supervision polls, the panel sends an SDI Failure Report
to the receiver. If it fails to communicate with the
D9133,
SERVC SDI 80
displays at the command
center. The SDI Failure Report includes the address of
the troubled module to indicate which module needs
service.
11.6
SDI Address 88
SDI Address 88 is available with the D9412G/D7412G
panels and is used for several different applications.
When using SDI Address 88, only connect one listed
devices at a time.
11.6.1
D9133DC Direct Connect Programming
Module
Use the D9133DC Direct Connect Programming
Module to locally program the D9412G/D7412G panels.
In addition, the D9133DC allows diagnostic and history
retrieval. D9133DC is not UL Listed.
Connecting the D9133DC
1.
Configure D9133DC for SDI Address 88. To
program the panel when the reset pin is in the
unlocked position, program Enable SDI RAM to
Yes
in the RADXAUX1 handler.
2. Connect D9133DC to Com Port 1 or Com Port 2
on the PC. The D9133DC has a DB-9 female serial
connector. A null modem cable must be purchased
separately to connect the D9133DC to a PC.
3. Using 0.8 mm (22 AWG) or 1.2 mm (18 AWG) wire,
connect the D9133DC SDI terminals (SDI PWR,
SDI A, SDI B, and SDI COM) to the panel’s SDI
terminals (Terminals 29 to 32).
To send or receive the panel’s program, place the Reset
Pin in the
Locked
or
Unlocked
position.
0101
0101
0101
Locking the Rest Pin when programming the
panel improves upload/download time.
Used as an External Modem
The D9133DC can operate as an external modem when
using RAM IV with the panel. See the D9412G/D7412G
Program Entry Guide for programming details.
Figure 28: D9133 Jumper Settings
1
2
3
4
80
Table 21: Access Control Module Address Switch
Settings
DIP Switch Settings
Door Module
Addresses
1
2
3
4
5**
6**
1
ON
ON
ON
*
ON
ON
2
OFF
ON
ON
*
ON
ON
-----------------------D7412G Maximum-----------------------
3
ON
OFF
ON
*
ON
ON
4
OFF
OFF
ON
*
ON
ON
5
ON
ON
OFF
*
ON
ON
6
OFF
ON
OFF
*
ON
ON
7
ON
OFF
OFF
*
ON
ON
8
OFF
OFF
OFF
*
ON
ON
*Switch 4, Fail Safe Mode:
ON = If SDI Bus fails, relay energizes
OFF = If SDI Bus fails, relay de-energizes
**Switches 5 and 6 MUST remain in the ON position.