D7024
| Operation and Installation Guide | 7.0 Control Panel Programming
Bosch | 7/05 | 31499J
53
4.
Press the number key corresponding to your
selection.
A window allowing you to enter hexadecimal digits
appears. The heading depends on the item you
previously selected:
5.
Enter the digit to be reported for the selected
condition by pressing a number key or a special
keys if a hexadecimal character is needed.
6.
Press [#] to access and the preceding display.
7.7.2
4/2 Report Codes
4/2 Report codes apply to system conditions only when
you select the 3/1 or 4/2 format. You can program two
digits sent for each condition.
Table 28
identifies the
reports you can program.
1.
Press [9] to allow you to program additional reports
2.
Press [9] to return to the preceding group of
reporting codes.
3.
Press the number key corresponding to your code
selection.
4.
A window allowing you to enter two hexadecimal
digits appears. The heading depends on the item
you previously selected:
5.
Enter the digits you want reported for the selected
condition by pressing a number key or one of the
special keys if a hexadecimal character is needed.
6.
Press [#] to access the preceding display.
Table 28:
4/2 Reports
Report
Description
System in Test, System in
Test Restore
Sent for Walt Test operations.
Silence
Sent when you press
[SILENCE].
Fire Drill, Fire Drill
Restore
Sent for fire drill operations.
Open Reset Report
Sent when you press [RESET].
Low Battery, Low Battery
Restore, AC Failure, AC
Failure Restore
Sent for power problems.
Test Report
Sent for manual or automatic
Communicator Tests.
Off-normal at Test
Sent if the control panel is off-
normal at the Automatic Test
time.
Phone Trouble, Restore
Sent for telephone line prob-
lems.
System Trouble, Restore
Sent for general system prob-
lems.
FIRE ALARM D1 ( )
0 THRU 9
<HISTORY>: A
<TEST>:
B
<DISABLE>: C
<DRILL>:
D
<SILENCE>: E
<RESET>:
F
4/2 RPT CODS
0- SYSTM IN TST
1- SYS TEST RST
2- SILENCE
3- FIRE DRILL
4- FIRE DRL RST
5- OPEN RST RPT
6- LOW BATTERY
7- LOW BATT RST
8- AC FAILURE
9- MORE
4/2 RPT CODS
0- AC FAIL RST
1- TEST REPORT
2- OFF NORM TEST
3- PHONE 1 TRBL
4- PN 1 TRB RST
5- PHONE 2 TRBL
6- PN 2 TRB RST
7- SYSTEM TROUB
8- SYS TRB RST
SYSTM IN TST ( )
0 THRU 9
<HISTORY>: A
<TEST>:
B
<DISABLE>: C
<DRILL>:
D
<SILENCE>: E
<RESET>:
F