| Operation and Installation Guide | 6.0 Programming
30
Bosch | 7/05 | 31499J
6.0
Programming
6.1
Point Programming
6.1.1
Point Functions Overview
Each point in the system can be programmed with its own characteristics. Point functions simplify the point
programming by allowing you to define a common set of characteristics for similar points, and assigning those
characteristics to selected points as a point function. There are 16 point functions, each with programmable
configuration features (such as fire, waterflow, and so on), local only operation, silencing, and loop response.
Each point is assigned to use the characteristics of one point function and then programmed for additional
characteristics, such as response to an open circuit, enabled status, output zone, verification, latching, and point
description.
For example, you can determine you have the following functions:
•
1 = Pull Station
•
2 = Smoke Detector
•
3 = Reset Keyswitch
•
4 = Silence Keyswitch
•
5 = Supervisory Input
•
6 = Monitor Input
•
7 = Local Test
•
8 = Waterflow Sensor
Refer to
Table 16
for the characteristics that correlate with each function.
After any programming change, and especially after remote programming changes, a complete functional
checkout of the control panel’s operation is required. Hazards to life and property can occur if the system
is not tested to detect possible improper programming.
When programming the system, enter only valid information within the ranges specified in the program-
ming table. Incorrect programming causes improper system operation. While using built-in programming,
invalid input values might not be rejected in every case. Ensure that only the intended values are entered
while programming to prevent improper system operation.
Before programming the control panel, determine the types of functions required and map the input points
to the functions.
Table 16:
Point Function Characteristics
Function
Configuration
Local Only?
Silenceable?
Loop Resp.
1. Pull Station
Fire
No
No
Fast
2. Smoke Detector
Fire
No
No
Fast
3. Reset Keyswitch
Reset
Yes
No
Fast
4. Silence Keyswitch
Silence
Yes
No
Fast
5. Supervisory Input
Supervisory
No
Yes
Fast
6. Monitor Input
Monitor
Yes
Yes
Fast
7. Local Test
Fire
Yes
Yes
Fast
8. Waterflow Sensor
Waterflow
No
No
Programmed