6 720 821 651 (2017/05)
CRC200
8 | Installation
•
The installation location (= reference room) must be
suitable for controlling the zone (
Fig. 5, Page 8).
•
The user interface must be installed on an interior wall.
•
Do not place obstructions within 2 1/2' (0.75 m) below
CRC200.
Fig. 5
Installation location in the reference room
If there is no suitable reference room, we
recommend changing the settings to a purely
outdoor temperature dependent control.
6 720 811 153-03.1O
≥ 4'
(≥ 1.2 m)
2'
(0.6 m)
≥ 3 1/4'
(≥ 1 m)
2 1/2'
(≥ 0.75 m)
Summary of Contents for CRC200
Page 32: ......