Inspection and maintenance
41
Condens 7000 F – 6720871560 (2019/11)
11.11 Replacing components
NOTICE:
Malfunctions due to incorrectly connected or unconnected hose
lines!
If the wrong hose lines are used or if they are incorrectly connected, this
leads to unhygienic combustion.
▶ Connect the hose lines as shown in the connection diagram
(
▶ Make sure the hose lines are not buckled or trapped.
11.11.1 Removing the air/gas ratio control valve
Observe replacement interval of the air/gas ratio control valve.
▶ Replace air/gas ratio control valve depending on the service life
according to tab. 14, page 42.
▶ Shut down the heating system (
Chapter 9.1, page 30).
▶ Close the main gas shut-off valve or gas isolator and secure against
unintentional re-opening.
▶ Remove the front panel (
▶ Undo the hose clip and pull off the compensation test cable [1]
at the valve.
▶ Remove the plugs of the solenoid valves at the air/gas ratio control
valve and valve testing system [4].
▶ Undo the union nut on the gas supply pipe [2].
▶ Undo the 4 screws [5] on the flanges [3] of the air/gas ratio control
valve at the top and bottom.
▶ Remove the air/gas ratio control valve.
Fig. 57 Undo the air/gas ratio control valve connections
(150 ... 300 kW)
[1]
Compensation test cable
[2]
Gas supply pipe union nut
[3]
Flange
[4]
Plug for solenoid valves
[5]
Screws (4 x) top and bottom
[6]
Test cable for gas outlet pressure
Fig. 58 Undo the air/gas ratio control valve connections
(75 ... 100 kW)
[1]
Compensation test cable
[2]
Gas supply pipe union nut
[3]
Flange
[4]
Plug for solenoid valve
[5]
Screws (4 x) top and bottom
[6]
Test cable for gas outlet pressure
11.11.2 Removing the fan
▶ Shut down the heating system (
Chapter 9.1, page 30).
▶ Close the main gas shut-off valve or gas isolator and secure against
unintentional re-opening.
▶ Remove the front panel (
Chapter 11.1, page 31).
▶ Detach the electrical connections at the fan (
▶ Disconnect the plug-in connector (
Fig. 59)
With room sealed operation:
▶ Release the hinged pipe clip on the supply air hose
(
▶ Pull off supply air hose together with the connector from the
ventilation air collector (
Fig. 42, page 36).
Fig. 59 Electrical connections, removing the fan
(boiler rating 75-100 kW)
[1]
Hexagon nuts (4x) on the mixture manifold
[2]
Electrical connections on the fan, boiler rating 75-100 kW
[3]
Union nut on venturi, boiler rating 75-100 kW
[4]
Plug-in connector, boiler rating 75-300 kW
0010012557-001
5
5
4
4
3
6
1
2
0010013913-001
2
1
3
4
5
6
5
0010015320-001
1
2
3
4