Briefing the user, handing over technical documents
Condens 7000 F – 6720871560 (2019/11)
30
7.16
Checking tightness during operation
NOTICE:
Risk of material damage due to a short circuit!
▶ Prior to checking for leaks, cover areas at risk, e.g. the internal water
pressure sensor and the return temperature sensor in the boiler
return.
▶ Never spray or allow leak detection agent to drip onto cable entries,
plugs or electrical cables.
▶ To prevent corrosion, carefully wipe off the leak detection agent
afterwards.
▶ With the burner operational, use a foaming agent to test all joints
along the entire burner path, such as:
• Test nipple
• Locking screw for gas supply pressure
• Screw fittings (also at the gas connection) etc.
The agent must be approved for gas tightness testing.
7.17
Installing casing parts
Fig. 32 Installing casing parts
[1]
Bottom panel
[2]
Front panel at bottom
[3]
Front panel at top
[4]
Side panels at front
[5]
Side panels at rear
▶ First hook the side panels at the rear [5] into the bottom rail at the
bottom, then lift them slightly and hook in at the top.
▶ Using fixing screws, secure the rear side panels [5] to the rear of the
boiler.
▶ First hook the side panels at the front [4] into the bottom rail at the
bottom, then lift them slightly and hook in at the top.
▶ Insert the bottom panel [1].
▶ Hook the bottom boiler front panel [2] into the cutouts at the bottom
of the boiler casing and hook into the side panels.
▶ Insert the upper boiler front panel [3] into the lower boiler front panel
and place against side panels.
▶ Make sure that bolts at the top have engaged in the corresponding
holes.
▶ Turn the unlocking screws on the top of the boiler clockwise using a
suitable tool and lock the front panel [3].
▶ Affix the clear pocket containing the technical documentation to the
side panel of the boiler in a clearly visible location.
8
Briefing the user, handing over technical
documents
WARNING:
Danger to life due to poisoning!
Risk of poisoning due to escaping flue gases when the air supply is
inadequate.
▶ Make sure that a supply of air is available in every operating mode
through corresponding openings to the open air.
▶ Make the user aware of the need for and function of the ventilation
and combustion air apertures.
▶ Make the user familiar with the heating system and the boiler
operation.
▶ Make the user aware that the boiler and control unit must only be
opened by qualified contractors.
▶ Confirm commissioning in the report (
Chapter 17.6).
▶ Together with the user and referring to the operating instructions,
perform a shutdown and restart.
▶ Point out the user that frequent refilling of heating water is a sign that
the system is faulty and/or leaking (ensure required water quality
according to the operator's log).
▶ Inform operator about the required water quality and point out where
the heating water must be refilled.
▶ Explain to the customer what to do in an emergency, e.g. a fire,
referring to the operating instructions.
▶ Hand over the technical documents to the user.
9
Shutdown
NOTICE:
Frost damage!
The heating system can freeze up when it is not in operation.
▶ Whenever possible, leave the heating system permanently
switched on.
▶ Protect the heating system against frost by draining the heating
system and DHW pipes from the lowest point.
9.1
Shutting down the heating system via the control unit
▶ To shut down the heating system, observe the corresponding
technical documentation for the control unit.
▶ Close off the fuel supply.
9.2
Shutting down the heating system in an emergency
Only in emergencies, shut down the heating system via the fuse/circuit
breaker at the installation location or the heating system emergency stop
switch.
Explain to the operator/user what to do in an emergency, e.g. fire.
▶ Never risk your own life. Your own safety is paramount.
▶ Close off the fuel supply installed on site.
▶ Isolate the heating system from the mains power supply via the
heating system emergency stop switch or the main circuit breaker.
0010012502-001
4
4
2
3
5
5
1