Classic
L
ine TriTech CM
-
Passive Infrared Detector/Microwave
Intrusion Detector
Installation Instructions
BOSCH
2
Installation Considerations
Not suitable for outdoor use (2-1 ).
Never install the detector where the PIR or microwave
is in constant alarm (LED on). The LED is off when
properly installed.
Point away from outside traffic. Microwave energy
passes through non-metallic walls.
Point away from direct and indirect sunlight (2-2).
Point away from glass or other objects that rapidly
change temperatures (2-3, 2-4, and 2-5).
Point away from rotating machines (fans) (2-6).
Mount the detector on a solid and vibration free surface.
Secure drop-ceiling tiles, if the area above the tiles is
used as an air return for heating, ventilating, and air
conditioning (HVAC) systems.
Avoid mounting the detector within 1 ft (0.3 m) of any
fluorescent light fixtures.
warning!
Apply power only after all connections are made and
inspected. Do not coil excess wiring inside detector.
6
Wiring
Termlnal Label Function
1
(-) Input power: Use at least a 22
2
(+) AWG (0.8 mm) wire pair between
the unit and the oower source.
3
NO Alarm relav
4
C
Alarm relav
5
NC Alarm relav
6
T
Tamper
7
T
Tamper
8
M Memory input (refer to
Section 7
Other Features)
r
9
LED Display
LED
Cause
Steady blue
·
Dual alarm
Steadv vellow Microwave activation (walk test}
Steadv red
PIR activation (walk test\
\. Flashino blue Warm-uo oeriod after oower uo
10
Optical Module Adjustment
The PIR zones of the detector are divided into three
groups. Use the PIR adjustment knobs (10-1) to
independently adjust each group vertically to provide
the best coverage within a room. Two coverage
patterns are shown (10-2).
If targeted coverage is required for part of the area,
adjust the optical modules for the correct coverage.
For example (10-3): The detector is mounted 12 ft
(3.7 m) above the floor. The distance to one wall is 20 ft
(6.1 m) and 35 ft (10.7 m) to the opposite wall. Using
the
Optical Module Adjustments Table (10-4),
set the
optical module for the 20 ft (6.1 m) range to "D" and the
optical module for the 35 ft (10.7 m) to "I". Refer to
(10-5) for the maximum range and (10-6) for the
mounting height.
Note: The range shown in (10-4) is the distance from
the detector to the outside edge of the coverage
pattern.
Two coverage patterns are shown (10-3).
"'
1
Specifications
Dimensions:
Versions:
Coverage:
Input Power:
Height: 3.5 in (8.9 cm)
Diameter: 7 in (17.8 cm)
DS9370/DS9370E/DS9370E-C: Pearl white
DS9371/DS9371 E: Black
360
°
by up to 16.5 m (54ft) diameter coverage. Coverage may vary depending upon application conditions such as room temperature, building and
furnishings construction materials, and regulatory requirements. The pattern consists of 69 zones grouped into 3 sets of 23 zones.
Each set covers one-third of the 360
°
coverage pattern. Each set also has a vertical adjustment for precise pattern alignment.
9 VDC to 15 VDC nominal, 28 mA maximum current.
Standby Power:
Sensitivity:
Alarm Relay:
Tamper:
Supervision
Features:
Temperature
Range:
Microwave
Frequencies:
Compllance:
Certifications:
Other:
3
There is no internal standby battery. An external standby battery capacity of 29 mAh is required for each hour of standby time needed. For UL, 4 h (116 mAh)
must be provided by the control unit. The products are intended to be powered by a power-limited output of a UL/cUL Listed Burglar Alarm control unit, or via
a Listed UL603/ULC-S318 Class 2 power limited power supply, capable of 4 hours of standby power. Check standby battery annually.
Low and high settings.
Silent-operating Form "C" relay. Contacts rated 100 mA, 28 VDC, 2.8 W maximum for DC-resistive loads. The contacts transfer on alarm for a period of 4
sec. Note: Do not use with capacitive or inductive loads.
Normally closed (NC), with cover on. A ceiling tamper is included for surface mounting. Contacts rated at 28 VDC, 100 mA, 3 W maximum.
Microwave: The complete circuit operation of this subsystem is checked approximately every 4 h.
PIR: The detector defaults to PIR technology protection if the microwave subsystem fails. The detector indicates an alarm using the green LED only and
activates the alarm relay.
FCC: +5
•c
to +50
•c
(41
°
F to 122 °F) CE (excluding France, UK): -10
•c
to +55
•c
(14
°
F to 131
°
F)
CE France: 5
°
C to +40
•c
(41
°
F to 104 °F) UL:
o •c
to +49
•c
(32
°
F to 120
°
F)
DS9370/DS9371: 10.525 GHz (UL Listed).
DS9370E/DS9371 E: 10.510 to 10.580 GHz
DS9370E-C: 10.570 to 10.610 GHz
DS9370/DS9371 complies with Part 15 of the FCC Rules. Operation is subject to two conditions:
1. This device cannot cause harmful interference.
2. This device must accept any interference, including interference that might cause undesired operation. Changes or modifications not expressly
approved by Bosch Security Systems can void the user's authority to operate the equipment.
UL / CUL, FCC ISED: DS9370, DS9371, CE: DS9370E, DS9370E-C, NF
&A2P: Env. Class I Grade 2 EN 50131-2-4 ( DS9370E-C), Env. Class II Grade 2
EN 50131-2-4 (DS9370E) Product must be tested at least once each year. All wiring must be in accordance with: the National Electrical Code
(ANSI/NFPA70); Local codes and the authorities having jurisdiction.
Coverage Patterns
5
Mounting
Microwave coverage
-
PIR coverage
Typical coverage pattern shown for 12 ft (3.7 m) mount
ing height with optical adjustments set to "I" (refer to
Section 10 Optical Module Adjustment).
4
Coverage Pattern Masking
1. Select a mounting location. Mount the sensor where an intruder is most likely to cross the coverage pattern
(5-1).
2. Mount the detector 8 ft to 20 ft (2,4 m to 6.1 m) above the floor, 12 ft (3.7 m) recommended (5-2).
3. To open the detector, locate the arrow (5-3) on the cover of the detector. Insert a flat head screwdriver in the
recess (5-4) between the cover and the base and twist. One side of the cover remains attached to the base of
the detector.
4 Optional: Remove the cover from the base. Grasp the top of the cover with one hand while holding the base
with the other (5-5).
5. Gently push the cover to one side (5-6) while twisting the cover back and away from the base (5-7).
Note: Ensure all wiring is de-energized before routing.
6. Route wiring as necessary to the rear of the base and through the center hole (5-8) or wire entrance for sur-
face mounting (5-9).
To reduce the detector's coverage area, use the masks
provided. The masking kit contains two 120
°
(4-1) and
two 90
°
(4-2) masks. You can mask:
- go• (4-6)
Note: Do not mount on removable ceiling tiles unless a sandwich is made of the base, ceiling tile, and a back plate
behind the tile.
- 120
°
(4-3)
- 180
°
(4-4)
- 210
°
(4-7)
- 240
°
(4-5)
- 330
°
Place the masks on the outside of the detector. Do not
open the detector and place the masks on the inside.
Note: Masking does not affect the microwave
coverage.
r
7
Other Features
Memory, Night Mode, and Walk Test need a control
"'
voltage on Terminal 8 to activate these features (refer to
Table 1 ). The control voltage must be between 6 VDC
and 18
voe.
Use a supply voltage to apply a control voltage to
Terminal 8 (7-1).
Or, use a control panel or external DC power supply as
control voltage (7-2):
-
+6
voe
to +18 VDC
=
On (switch closed)
-
o voe=
Off (switch open)
Day Mode
Disables the alarm memory and
allows the LED (if activated) to
operate normally.
Memory
When the detector is in Night Mode,
the memory activates. The detector
stores an alarm for display when
switched to Day Mode.
Note: The LED jumper must be in the
On position (8-5).
Night Mode
Enables the alarm memory and
disables the LED operation.
Remote Walk Remotely enable the LED operation
Test
from Terminal M for walk testing. Use
this feature when the LED jumper is in
the Off position (8-6).
iTable 1: Mode Switching
Action
Control Voltage
LED
I
fTermlnal Ml
Jumper
Turn on Night Mode On for more than 20 On
sec
Tum off Night Mode
and display stored
Off from Night Mode On
alarm
On for more than 5
Reset stored alarm
sec or enter Night
On
Mode
Tum on Remote Walk On for more than 5
Test
sec, but less than
Off
20 sec
Tum off Remote Walk On for more than 1
Test
sec, but less than
Off
20 sec
\.
�
7. Firmly mount the base using the mounting holes (5-10, 5-11) and one of these options:
Depending on local regulations, mount the base directly on the surface using anchors, mollies, or wing
nuts.
Mount the detector on an electrical box.
Connect the detector directly to short lengths of electro-magnetic tubing (EMT), 0.5 in. (1.27) cm (short
enough to avoid movement of the detector). Use the wire entrance for the EMT (5-8).
Note: Use the curved mounting slots (5-11) to rotate the detector up to 60
°
to establish the best coverage.
8. If a ceiling tamper is needed, remove the tamper post (5-12) by tapping it gently with a hammer to detach it
from the three tabs.
9. Mount the post to the ceiling using the #8 screw provided (5-13).
10. Attach the cover if removed, and close it.
11. Secure the entire assembly with the supplied anti-vandal screw (5-14 ).
12.Use the cable ties (5-15) for strain relief.
r
8
LED Operation
Feature
Setting
Description
PIR Sensitivity
Selection Pins (8-1)
Low (8-2) Recommended setting for most installations. Tolerates environmental
extremes.
Note: The detector is shipoed in Low Sensitivitv mode.
High (8-3) Use this setting if more sensitivity is needed.
Note: This setting is more sensitive to environmental changes that can cause
false alarms.
LED OnlOff Pins
(8-4)
On (8-5) Operates the tri-color LED.
Off (8-6) If LED indication is not wanted after set up and walk tests are complete, place
in the Off position.
No jumper across the On or Off pins disables the LED.
r
11
Walk Test
Note: Ensure the LED jumper is set to on (8-5).
Note: To avoid false alarms, set the microwave range
(11-1) to its minimum setting before starting the Walk
Test.
1. Wait at least 2 minutes after power up to start the
Walk Test.
The blue LEDs flashes until the detector stabilizes
and no movement is detected for 2 seconds.
2. Watch the LED as you walk towards the edge of the
pattern (11-2). The LED lights at the outside edge of
the coverage range.
The red LED lights, identifying the PIR pattern edge.
The yellow LED lights, identifying the microwave
pattern edge.
The blue LED indicates alarms in both the micro
wave and PIR mode.
4. Repeat Step 3 from different directions until you
adequately verify the coverage pattern.
5. If the required microwave coverage is not achieved,
increase the microwave adjustment (11-1) by turning
it clockwise slightly. Wait 1 min after adjusting the
microwave range before continuing the Walk Test.
'\..
Note: Do not adjust the microwave range higher than
needed.
Product must be walk tested at least once each year.
r
Bosch Security Systems, B.V.
Torenallee 49
5617 BA Eindhoven
Netherlands
www.boschsecurity.com
© 2021 Bosch Security Systems, B.V.
F.01U.384.349 -16
2021.01
"I
Page 3 of 10