![Bosch B4512 Owner'S Manual Download Page 130](http://html.mh-extra.com/html/bosch/b4512/b4512_owners-manual_39267130.webp)
Test
Use the Test menu to walk test your system, send test
reports, or to review system revision information on the
keypad display.
Walk Test
A walk test allows you to test the sensors, keypads,
sounders, and other devices in your system without
creating alarm events. You can review untested points
at the keypad to help pinpoint any problems.
You cannot turn on the security system while in the walk
test mode. Also, the security system does not create
alarm events for points included in the walk test. Points
not included create alarm events. For example, faulting
a fire point during an intrusion walk test creates a fire
alarm event.
Beginning the walk test activates the burglary tone for 2
seconds. A battery test also begins. A successful battery
test ends in four minutes (the walk test continues). If
the security system determines there is a low battery, it
generates a low battery event and continues the test. If
the battery is determined to be very low, the system
creates a missing battery event and ends the battery
test immediately.
24.3
24.3.1
130 en | B920 Actions menu