64
en | System limits
AVENAR panel
2022-07 | 5.0 | F.01U.378.910
System manual
Bosch Sicherheitssysteme GmbH
Module
Device
Max. number Further information
FMF-ADP-TTY
FMF-ADP-FBF
FMF-FAT
4
FMF-FBF-FAT
4
FLM-420-I8R1-S
FCS-LHD-2EN
1
Altogether only 200 LSN devices
including max. 2 EOL modules on
the same LSN bus
No pre-alarm
LSN 0300 A
LSN 1500 A
FLM-420-RLE-S
8
Max. number is valid for fire
extinguishing systems
FNX-425U
84/127
Up to 84 elements per loop
Up to 127 elements per loop if
operated without detector
FWI-270
10
Any manual call point 21
FLM-420-EOL2W-W
FLM-420-EOL4W
10
FWI-270
FDOOT271-O
FDM273-O
FDM275-O
30
NZM 0002 A
SOL-LX
11
1 Hz
18
0.5 Hz
PA 5
2
PA 10-SSM
1
7.4
Power loss of panel components
i
Notice!
Power loss of components (typical)
In the data sheet of the system you will find more detailed information on the listed typical
power loss values.
Component
Power loss
ANI 0016 A
0.62 W (all LEDs lit)
BCM‑0000‑B
–
0.96 W (cont green LED lit)
–
1.44 W (per AUX with 1.06 A load)
CZM 0004 A
–
1.65 W (for a line with 100 mA load)
–
3.36 W (for 4 lines with 100 mA load each)
ENO 0000 B
–
1.44 W (1 relay activated)
–
7.80 W (4 relays act key deposit heating
active)
FPE-2000-PPC
max. 10 W