![Bosch AVENAR panel System Manual Download Page 57](http://html.mh-extra.com/html/bosch/avenar-panel/avenar-panel_system-manual_44768057.webp)
AVENAR panel
Maintenance and service | en
57
Bosch Sicherheitssysteme GmbH
System manual
2022-07 | 5.0 | F.01U.378.910
Documentation
The installation instructions and operating instructions supplied with the device are available
as PDF files at www.boschsecurity.com.
Additional documents (including the Wiring guide) are available to those with access rights at
the extranet.
i
Notice!
The hexadecimal error codes can be found at the extranet (access rights required): LSN
diagnostic data (F.01U.081.090).
!
Warning!
The power button must be used to switch off the device before removing the power supply. It
may not be disconnected from power supply while system is running. The device may be
damaged if this procedure is violated. Not following this procedure may result in loss of
warranty. Refer to user guide for further information.
i
Notice!
The description of security item types can be found on the Extranet (access right required):
Security item types (F.01U.353.668).
6.1
Replacement of FPA panel controller
Due to its modular design and compatible architecture, an FPA fire panel can be upgraded
with the latest AVENAR panel controller.
Consider the following checklist upfront:
Address cards
AVENAR panel does not require address cards.
–
Make sure to order an AVENAR panel controller containing the right software license.
–
Check if the fire panel has an interface to:
–
Building management system via BIS, OPC or FSI
–
Hierarchy panel (UGM-2040)
–
Voice alarm system (Smart Safety Link)
–
A premium license is required for:
–
A panel that needs to be available in a building management system or hierarchy
panel
–
A panel that is physically connected to a voice alarm system
–
Concerning the detection points, no further action is necessary.
–
After the replacement, the address cards can be disposed in compliance with the
applicable local regulations and directives.
Short rail
–
Use AVENAR panel controllers only in combination with the short rail PRS-0002-C.
–
Exchange the short rail when the panel is equipped with a PRS 0002 A. Not exchanging
the short rail will generate faults.
Battery controller module
–
AVENAR panel cannot comply with EN 54-4 when the panel contains the legacy battery
controller BCM-0000-A.
–
Replace all BCM-0000-A by BCM-0000-B battery controller modules.
RS232 interface
AVENAR panel does not contain an integrated RS232 serial port anymore.