en | Installing
Access Modular Controller 2
2022-03 | V03 |
Installation manual
Bosch Security Systems B.V.
–
Door open: R
S
+ R
P
–
Door closed: R
S
–
Open wire: R
S
+ R
P
= ∞
–
Short circuit: R
S
+ R
P
= 0
The resistor values can vary and depend on the used lock system.
The extension package includes 2.2 kΩ resistors which can be used to replace R
S
and R
P
resistors.
To detect the four states, the voltage drop in the connecting cable may not exceed special
values. The following table shows the maximum values of permissible cable resistance
depending on the used resistor combination.
R
p
1k
1k2
1k5
1k8
2k2
2k7
3k3
3k9
4k7
5k6
6k8
8k2
R
s
1k
220
220
220
210
200
1k2
260
270
270
270
260
240
1k5
310
330
340
350
350
340
310
280
1k8
340
380
390
410
410
410
400
370
330
290
200
2k2
430
460
490
510
520
510
500
460
420
340
240
2k7
490
540
570
620
630
640
640
620
580
510
420
3k3
610
650
700
740
770
780
770
750
700
620
3k9
720
790
850
890
910
910
910
880
810
4k7
880
960
960
970
1100
1100
1050
1050
5k6
1050
1100
1200
1200
1300
1300
1250
6k8
1300
1400
1500
1500
1500
1500
8k2
1500
1650
1700
1800
1900
Table 4.3:
Maximum values of cable resistance per used resistor combination in Ohm
i
Notice!
We recommend using serial resistors (R
S
) no higher than 5K6 in order to obtain clear
measurements.