Installation and start-up of UPS B8000FXS 10-60kVA
Installazione e avviamento UPS B8000FXS 10-60kVA
56
OMD91050 REV. G
5.5 SWITCHING
PROCEDURE TO MANUAL BYPASS
The load is transferred to Manual Bypass with no interruption of supply to the loads. In this
configuration, the system can be restarted via the return procedure from load on manual
bypass, without the need to de-energize the loads.
Manual bypass
To perform the switching procedure correctly, make sure no alarms are present on
the system.
During Manual Bypass the load is supplied directly by the input mains, therefore
continuous supply cannot be guaranteed to the loads.
No.
ACTION
LCD DISPLAY
OPERATING CHECKS
1
Move the
bypass
selector SW
to BYPASS
A30 GENERAL ALARM
The load is transferred to the bypass
line. LED #5 off, LED #6 lit orange.
2
Close MBCB
A30 GENERAL ALARM
The inverter is switched off. The load is
supplied by the input mains through the
manual bypass switch. The static
bypass switch is still closed. Led #8 lit
orange.
3
Open BCB
A30 GENERAL ALARM
The battery is disconnected from the DC
bus bar. Led #4 red flashing.
4
Open RCB
A30 GENERAL ALARM
The supply input is opened; the rectifier
shuts down. LED #1 off.
5
Open OCB
A30 GENERAL ALARM
The load remains fed by the manual
bypass switch. LED #8 off.
6
Open SBCB
A30 GENERAL ALARM
The bypass line is disconnected. The
display goes out.
7
BLANK
The load is supplied directly by the
mains through the manual bypass
switch. The UPS is isolated.
Only for B8033FXS 30...60kVA with back-feed protection option:
Open F12
Sectioning phase R - Power supply
contactor back-feed / relay contact RL1
PB244 back-panel board
Summary of Contents for ASD91
Page 1: ...OPERATING MANUAL UPS MANUALE OPERATIVO UPS B8000FXS 10 15 20 30 40 50 60kVA ...
Page 2: ......
Page 4: ......
Page 6: ...Warnings and general information Avvertenze e informazioni generali 2 OMD91048 REV B ...
Page 134: ...UPS user manual Utilizzo dell UPS 6 OMD91052 REV C ...
Page 135: ...UPS user manual Utilizzo dell UPS OMD91052 REV C 7 ENGLISH LANGUAGE ...
Page 181: ...UPS user manual Utilizzo dell UPS OMD91052 REV C 53 LINGUA ITALIANA ...