Installation and start-up of UPS B8000FXS 10-60kVA
Installazione e avviamento UPS B8000FXS 10-60kVA
28
OMD91050 REV. G
To protect the output against electrical shock, use the following residual current devices:
B8033FXS: DEVICE AS TYPE B (IEC/TR 60755/A2)
B8031FXS: DEVICE AS TYPE A (IEC 61081-1 or IEC 61091-1)
Electrical connection data
Power (kVA)
10 15 20
B8031FXS
Input Fuses (A)
Rectifier 3x25
3x32
3x32
Bypass 1x80
1x110
1x150
Input cables
(mm
2
)
Rectifier 4x6
4x10
4x10
Bypass 2x16
2x25
2x35
Output cables
(mm
2
)
2x16
2x25
2x35
Battery cables
(mm
2
)
3x6
3x6
3x6
Ground cable
(mm
2
) 16
16
16
Electrical connection data
Power (kVA)
10 15 20 30 40 50 60
B8033FXS
Input Fuses (A)
Rectifier
3x25 3x32 3x32 3x70 3x70 3x100
3x135
Bypass
3x25 3x32 3x32 3x70 3x70 3x100
3x135
Input cables
(mm
2
)
Rectifier 4x6
4x6
4x10
4x25 4x25 4x35 4x35
Bypass 4x6
4x6
4x10
4x25 4x25 4x35 4x35
Output cables
(mm
2
)
4x6 4x6 4x6 4x10 4x25 4x25 4x35
Battery cables
(mm
2
)
3x6 3x6 3x6
3x6
3x16 3x16 3x35
Ground cable
(mm
2
)
6 6 10 16 16 16 16
Summary of Contents for ASD91
Page 1: ...OPERATING MANUAL UPS MANUALE OPERATIVO UPS B8000FXS 10 15 20 30 40 50 60kVA ...
Page 2: ......
Page 4: ......
Page 6: ...Warnings and general information Avvertenze e informazioni generali 2 OMD91048 REV B ...
Page 134: ...UPS user manual Utilizzo dell UPS 6 OMD91052 REV C ...
Page 135: ...UPS user manual Utilizzo dell UPS OMD91052 REV C 7 ENGLISH LANGUAGE ...
Page 181: ...UPS user manual Utilizzo dell UPS OMD91052 REV C 53 LINGUA ITALIANA ...