Setting all the parameters
To save all the parameters it is necessary to reach the end of the guided procedure
until the last screen previously shown.
If the procedure is interrupted earlier, none of the parameters previously set will be
saved.
6.5
SETTING THE MODBUS PARAMETERS
The parameters regarding the communication via RS485 interface can be set in the
MODBUS menu.
Modbus address
MODBUS ADDRESS
The single digits can be modified via the arrow
keys (
/
) and confirmed by pressing
(ENTER).
202
Parameter
Standard
Range
MODBUS ADDRESS
1
1 …. 247
6.6 UPS
TEST
The UPS TEST menu allows to carry out a switching test of the inverter. The inverter is
switched off and the load is transferred to the bypass supply. The inverter supply is
automatically restored after a few seconds.
UPS TEST?
The value on the second line is ready to be
changed
NO
(1x)
UPS TEST?
The parameter is changed. The change is
confirmed by pressing
(ENTER)
YES
SPECIAL
The system performs a test and returns to the
previous screen
UPS TEST
Possible loss of supply
In case of power failure while the test is being performed, the immediate operation of
the inverter is not guaranteed.
Summary of Contents for ASD91
Page 1: ...OPERATING MANUAL UPS MANUALE OPERATIVO UPS B8000FXS 10 15 20 30 40 50 60kVA ...
Page 2: ......
Page 4: ......
Page 6: ...Warnings and general information Avvertenze e informazioni generali 2 OMD91048 REV B ...
Page 134: ...UPS user manual Utilizzo dell UPS 6 OMD91052 REV C ...
Page 135: ...UPS user manual Utilizzo dell UPS OMD91052 REV C 7 ENGLISH LANGUAGE ...
Page 181: ...UPS user manual Utilizzo dell UPS OMD91052 REV C 53 LINGUA ITALIANA ...