PowerSure
™
PST
Quick-Start Guide for 500-650VA; 230V
W
HAT
’
S
I
N
T
HE
B
OX
• Quick-Start guide
• PowerSure family user manual
• Warranty card
• USB cable (PAXXX-230U models only),1.8m (6ft.)
• RJ-11 cord, 2.1m (7 ft.)
• Two (2) 10A output power cords, 2.0m (6.6 ft.)
For more details, refer to the PowerSure user manual on CD.
Pour de plus amples informations, voir le manuel
d'utilisateur de la gamme des produits PowerSure sur CD.
Para una información más detallada, consulte el manual
del
usuario de la familia PowerSure en el CD.
Per informazioni ulteriori e più particolareggiate, consultare
il manuale dell'utente delle attrezzature PowerSure
contenuto sul CD.
Ausfuhrlichere Informationen finden Sie im Benutzerhandbuch der PowerSure-Familie auf CD.
Refer to Bottom for
Cautionary Markings
* Power ON/OFF/
Alarm Silence
Mains/Battery Indicator (Green) *
***USB port
(for PAXXX-230U models only)
Circuit
protector
** Black output
receptacles
(surge protec-
tion only
)
Data Line **
Protection
Connectors
TOP OF UPS
LEFT SIDE
OF UPS
RIGHT SIDE OF UPS
** AC Inlet
For details, see
** Installation
*** Communications
** Orange output recep-
tacles
(battery backup
and surge protection)
Fault Indicator (Red/Green) *
I
NSTALLATION
Read all safety, installation and operating instructions in the PowerSure family user
manual on the included CD or at
www.liebert.com
before operating the UPS. Adhere
to all warnings on the unit and in the manual.
1. Install the UPS indoors in a controlled environment, where it cannot be accidentally turned
off. Place it in an area of unrestricted airflow around the unit, away from water, flammable
liquids, gases, corrosives and conductive contaminants. Maintain an ambient temperature
range of 0°C to 40°C (32°F to 104°F).
2. Connect equipment to the receptacles on the back of the PST with one of the two supplied
output cables. Computers and monitors should be connected to the orange receptacles for
battery backup and surge protection; other office machines that do not exceed the capac-
ity of the UPS may be plugged into either of the two black receptacles, which provide
surge protection only.
3. Connect an input cable removed from the load equipment to the PowerSure PST and to
the mains supply socket.
4. Connect Phone/Fax/DSL/Internet/Modem devices to data line connectors.
5. Press and release the ON/OFF/Alarm Silence button to turn on the UPS. The UPS will beep and the Mains Indicator will illuminate (green).
6. Turn on connected equipment.
Plug this type of equipment
into black receptacles ONLY
Plug computers, monitors,
routers and cash registers into
orange receptacles
Inkjet
printers
Scanners
Fax
machines
C
ONTROLS
AND
I
NDICATORS
This button controls output power to
the connected load and has three
functions:
•Turns the PowerSure PST ON
•Turns the PowerSure PST OFF
•Silences PowerSure PST alarms
TURN THE UPS ON:
Press and release the
main ON/OFF button to start the UPS. An
audible alarm will sound briefly.
TURN THE UPS OFF:
When the PST is ON,
hold the main ON/OFF button down for more
than 2 seconds to shut it down. An audible
alarm will sound briefly.
SILENCE AN ALARM:
When a UPS alarm is
active, press and release the main ON/OFF
button to silence the audible alarm (Excep-
tions: low battery, overload and overtempera-
ture). DO NOT hold the button down for more
than 2 seconds or the PST will shut down.
CHECK THE PST’S CONDITION:
Three sta-
tus indicators on the front of the UPS illumi-
nate to specify the status of the UPS (see
section for details).
S
PECIFICATIONS
Model Number
PA500-230U
PA500-230
PA650-230U
PA650-230
Model Rating
VA / W
500 / 300
650 / 360
DIMENSIONS: mm (in.)
Unit
W x D x H
168 x 250 x 95
(6.6 x 9.8 x 3.7)
168 x 250 x 95
(6.6 x 9.8 x 3.7)
Shipping
W x D x H
238 x 350 x 142
(9.4 x 13.8 x 5.6)
238 x 350 x 142
(9.4 x 13.8 x 5.6)
WEIGHT: kg (lbs)
Unit
4.7 (10.4)
5.7 (12.5)
Shipping
5.7 (12.5)
6.7 (14.8)
INPUT AC PARAMETERS
Surge Protection
220J
Rated Input
Voltage
230VAC
Voltage Range
Without
Battery Operation
180VAC - 264VAC (±6VAC)
Frequency
47 - 63 Hz (±0.4 Hz)
OUTPUT AC PARAMETERS
Output
Receptacles
(3) IEC-320-C13 (orange)
battery surge protection
(2) IEC-320-C13 (black) surge protection
Output Cord
2m (6.6 ft) detachable, w/IEC-320 (Wire
Type: 1mm
2
, H05W-F 3G)
Voltage (Battery
Mode)
230VAC (±8%)
Output Current
2.9 A
4.2 A
Waveform (Battery
Mode)
Stepped Sinewave
Frequency
(Battery Mode)
50/60 Hz (±1 Hz)
Overload Warning
>100%
Overload
Shutdown
>110%
BATTERY PARAMETERS
Type
Valve-regulated, nonspillable, lead acid
Quantity x Voltage
x Rating
1 x 12V x 5 Ah
1 x 12V x 7 Ah
Transfer Time
4 – 6 ms typical
Back-up Time:
At 25°C (77°F), resistive loading,
w/ fully charged batteries:
Full load
2 minutes
1 minute
Half load
8 minutes
8 minutes
Recharge Time
12 hours to 90% rated capacity, after full
discharge into resistive load
ENVIRONMENTAL
Operating
Temperature
0°C to +40°C
(+32°F to +
104°F)
Storage
Temperature
-15°C to +50°C
(+5°F to + 122°F)
Relative
Humidity
0% to 95%,
non-condensing
Operating
Elevation
Up to 3000 m
(10,000 ft.) at
35°C (95°F)
w/o derating
Audible Noise
< 40 dBA, at
1 meter
AGENCY
Safety
EN50091-1-1,
TUV/GS listed,
CE Compliance
Mark
Surge
EN61000-4-5,
Level 3,
Criteria A
ESD
EN61000-4-2,
Level 3,
Criteria A
Susceptibility
EN61000-4-3,
Level 2,
Criteria A
Electrical Fast
Transient/
Burst
EN61000-4-4,
Level 3,
Criteria A
Emissions
EN50091-2,
Class B
Harmonics
EN61000-3-2
Conducted
Immunity
EN61000-4-6
Flicker EN61000-3-3
Transportation
ISTA
Procedure 1A
C
OMMUNICATIONS
The PowerSure PST has a USB interface port
for communication that will work with the built-
in Microsoft Power Manager software on the
user’s PC, if the PC is so equipped. It will pro-
vide UPS status and manages the automatic,
orderly shutdown of the computer. The UPS
(USB) communications meets HID standard,
version 1.11. All USB models are compatible
with Microsoft Windows 2000, Windows XP
and Mac OS 10.2 or later. All USB models ship
with a 6 ft. (1.8m) USB cable.