![BONKOTE M12 Instruction Manual Download Page 15](http://html.mh-extra.com/html/bonkote/m12/m12_instruction-manual_2787144015.webp)
13
6-I
:
PID value manual setting
M12 controller is basically unnecessary PID setting because it comes standard with Auto Tuning function.
In case of Overshoot or special soldering work, you can set PID value by manual.
Please use PID manual setting with your convenience.
①
Proportional band
Default
:88
℃
Setting range
:0
~
1570
℃
(
type J
:
0
~
1200
℃
)
Higher set value can reduce overshoot, however, it makes temperature recovery time longer
and temperature reduction during soldering work larger.
Ⅰ
:
At the Operation mode, press
for 3 seconds while pressing
△
key.
is
indicated at PV display.
Ⅱ
:
Push key once, and is indicated at PV display.
Ⅲ
:
Enter the desired value by
△
key or
▽
key at SV display, then push key 6 times to
return to the operation mode.
②
Integration time
Default
:38
seconds
Setting range
:0
~
3600
seconds
Higher set value can reduce overshoot, however, it makes temperature recovery time longer
and temperature reduction during soldering work larger.
Ⅰ
:
At the Operation mode, press
for 3 seconds while pressing
△
key.
indicated at PV display.
Ⅱ
:
Push key 2 times, and is indicated at PV display.
Ⅲ
:
Enter the desired value by
△
key or
▽
key at SV display, then push
return to the operation mode.
Operation mode
⇒
Auto Tuning
⇒
Proportional band
⇒
Operation mode
Operation mode
⇒
Auto Tuning
⇒
Integration time
⇒
Operation mode