EM-RES-03
10/07
26
26 EM-RES-03
10/07
5.9.3
Emergency message, fault switch-off
As soon as a fault switch-off occurs in a slave frequency inverter, the emergency
telegram is transmitted. The emergency telegram marks the node ID for the identifi-
cation of the failed node via its identifier and the existing fault message via its data
contents (8 bytes).
The emergency telegram has the identifier 128 + node ID.
After a fault acknowledgment, another emergency telegram is transmitted, with the
data content (Byte 0 ...7) being set to "0" this time. This identifies the subscriber's
repeated readiness for operation. If a further fault occurs subsequently, it is transmit-
ted in a new emergency telegram.
The acknowledgment sequence is based on the definitions according to CANopen.
Data contents of the emergency telegram:
Emergency telegram
Byte Value
Meaning
0 0x00
low-byte Error-Code
1 0x10
high-byte Error-Code
2 0x80
Error-Register
3 0x00
-
4 0x00
-
5 0x00
-
6
0xnn
internal Error-Code, low-byte
7
0xmm internal Error-Code, high-byte
Bytes 0, 1 and 2 are firmly defined and compatible with CANopen.
Bytes 6/7 contain the product specific VECTRON error code.
Error-Code
= 0x1000
= general error
Error-Register = 0x80
= manufacturer-specific error
The explanation and description of the product-specific VECTRON error code can be
found in the annex "Error messages".